Novar 1xxx
KMB systems
59
31
÷
37
alarm thresholds: undervoltage,
overvoltage, THDI, THDU, CHL,
number of connections and
temperature
—
—
—
Ranges and units as in Table 4.7
not displayed if the alrm not set up
40 alarm instantaneous condition
Indicates current state of alarm.
43 section connection time (in
thousands of hours)
Display range 0.001 to 130
In effect for contactor group outputs only.
44 number of section connections (in
thousands)
Display range 0.001 to 4000.
In effect for contactor group outputs only..
45 instrument failure condition
46 instantaneous condition of control
time
time until next contactor group control
intervention in seconds
50 instrument address
(communication interface)
1 ÷ 254
1
1
51 communication rate
(communication interface)
4800 – 9600 –
19200 Bd
—
9600 Bd
52 communication protocol
(communication interface)
KMB(P0)
—
KMB(P0)
Modbus-RTU protocol not supported
55 power system frequency
A (auto) – 50 Hz –
60 Hz
—
A (auto)
56 average value evaluation moving
window size
1 minute ÷ 7 days
-
7 days
applies to average values of Acos, APac,
APre
57 minimum and maximum value
evaluation moving window size
1 minutes ÷ 7 days -
15 minutes
applies to these minimum and maximum
values: mincos, maxPac, maxPre,
maxdPre
58 Celsius/Fahrenheit temperature
display mode
°C – °F
-
°C
59 cooling enable threshold
+10 ÷ +60 °C
1 °C
+40 °C
not displayed if cooling output not
specified
60 heating enable threshold
-30 ÷ +10 °C
1 °C
-5 °C
not displayed if heating output not
specified
Содержание NOVAR-1 Series
Страница 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Страница 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Страница 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Страница 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Страница 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Страница 71: ...Novar 1xxx KMB systems 71 Novar 1214 S400 installation controller and contactors supllied from DC...
Страница 72: ...Novar 1xxx KMB systems 72 Novar1312 installation hybrid system with both thyristor switches and contactors...
Страница 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...