17
EN
G
L
ISH
“Default settings” (Menu M – 9 – 7)
Parameter
Menu level
Description
Display writing
Measurement
Value field
Database
Pr01
M
– 9 – 7 – 01
Ignition cycle maximum time
IGNIT MINUTES
Minutes
5
– 25
25
Pr02
M
– 9 – 7 – 02
Start time
START MINUTES
Minutes
0
– 12
2
Pr03
M
– 9 – 7 – 03
Time interval between the two brazier cleaning
operations
BRAZIER CLEANING
Minutes
3
– 240
50
Pr04
M
– 9 – 7 – 04
Screw feed motor reducer ON time in ignition
phase
IGNIT SCREW
Seconds
0.0
– 4.0
1,0
Pr05
M
– 9 – 7 – 05
Screw feed motor reducer ON time in start
phase
START SCREW
Seconds
0.0
– 4.0
0,8
Pr06
M
– 9 – 7 – 06
Screw feed motor reducer ON time in power 1
work phase
POWER 1 SCREW
Seconds
0.1
– 4.0
1,0
Pr07
M
– 9 – 7 – 07
Screw feed motor reducer ON time in power 2
work phase
POWER 2 SCREW
Seconds
0.1
– 4.0
1,5
Pr08
M
– 9 – 7 – 08
Screw feed motor reducer ON time in power 3
work phase
POWER 3 SCREW
Seconds
0.1
– 4.0
2,2
Pr09
M
– 9 – 7 – 09
Screw feed motor reducer ON time in power 4
work phase
POWER 4 SCREW
Seconds
0.1
– 4.0
2,9
Pr10
M
– 9 – 7 – 10
Screw feed motor reducer ON time in power 5
work phase
POWER 5 SCREW
Seconds
0.1
– 4.0
3,2
Pr11
M
– 9 – 7 – 11
Alarm delay
ALARMS DELAY
Seconds
20
– 90
30
Pr12
M
– 9 – 7 – 12
Brazier cleaning duration
BRAZIER CLEANING
Seconds
0
– 120
60
Pr13
M
– 9 – 7 – 13
Flue gas minimum temperature to consider the
stove on
THRESHOL MINIMUM
°C
40
– 180
43
Pr14
M
– 9 – 7 – 14
Flue gas maximum temperature
THRESHOL MAXIMUM
°C
110
– 250
250
Pr15
M
– 9 – 7 – 15
Flue gas temperature threshold for igniting the
exchangers
THRESHOL BLOWER
°C
40
– 210
60
Pr16
M
– 9 – 7 – 16
Flue gas intake device speed in ignition phase
IGNIT FL GASSPEED
Revs/min
500
– 2800
2200
Pr17
M
– 9 – 7 – 17
Flue gas intake device speed in start phase
START FL GASSPEED
Revs/min
500
– 2800
2000
Pr18
M
– 9 – 7 – 18
Flue gas intake speed in power 1 work phase
P 1 FLUE GASSPEED
Revs/min
400
– 2800
1700
Pr19
M
– 9 – 7 – 19
Flue gas intake speed in power 2 work phase
P 2 FLUE GASSPEED
Revs/min
400
– 2800
1900
Pr20
M
– 9 – 7 – 20
Flue gas intake speed in power 3 work phase
P 3 FLUE GASSPEED
Revs/min
400
– 2800
2100
Pr21
M
– 9 – 7 – 21
Flue gas intake speed in power 4 work phase
P 4 FLUE GASSPEED
Revs/min
400
– 2800
2200
Pr22
M
– 9 – 7 – 22
Flue gas intake speed in power 5 work phase
P 5 FLUE GASSPEED
Revs/min
400
– 2800
2300
Pr23
M
– 9 – 7 – 23
Exchanger 1 motor speed in power 1 work
phase
AIR 1 SPEED
Volt
65
– 225
190
Pr24
M
– 9 – 7 – 24
Exchanger 1 motor speed in power 2 work
phase
AIR 2 SPEED
Volt
65
– 225
195
Pr25
M
– 9 – 7 – 25
Exchanger 1 motor speed in power 3 work
phase
AIR 3 SPEED
Volt
65
– 225
200
Pr26
M
– 9 – 7 – 26
Exchanger 1 motor speed in power 4 work
phase
AIR 4 SPEED
Volt
65
– 225
205
Pr27
M
– 9 – 7 – 27
Exchanger 1 motor speed in power 5 work
phase
AIR 5 SPEED
Volt
65
– 225
225
Pr28
M
– 9 – 7 – 28
Flue gas intake device switch-off threshold (in
switch-off phase)
THRESHOL OFF
°C
50
– 250
70
Pr29
M
– 9 – 7 – 29
Flue gas intake device speed in brazier
cleaning phase
EXHMOTOR CLEANING
Revs/min
500
– 2800
2800
Pr30
M
– 9 – 7 – 30
Screw feed motor reducer ON time in cleaning
phase
SCREW CLEANING
Seconds
0.0
– 4.0
0,6
Pr31
M
– 9 – 7 – 31
Flue gas intake device encoder enabling
(UNUSED)
ENCODER
On
– off
On
– off
ON
Pr32
M
– 9 – 7 – 32
Screw feed brake time
BRAKE TIME
Seconds
0.0
– 0.5
0,2
Pr33
M
– 9 – 7 – 33
START phase time
START TIME
Seconds
0
– 60
30
Pr34
M
– 9 – 7 – 34
PRE-HEATING phase time
PRE-HEAT TIME
Seconds
0
– 255
0
Pr35
M
– 9 – 7 – 35
Flue gas intake device speed in START phase
START GASSPEED
Revs/min
500
– 2800
2800
Pr36
M
– 9 – 7 – 36
Flue gas intake device speed in PRE-
HEATING phase
PRE-HEAT GASSPEED
Revs/min
500
– 2800
2800
Pr37
M
– 9 – 7 – 37
Flue gas intake device speed in FLAME
STAND-BY phase
STAND-BY GASSPEED
Revs/min
500
– 2800
2200