20
TEstop
T2
Resume
Off
Decrease
TEdown
TEH2
Hold
Off: Compressor stops.
Decrease: Decrease the running frequency to
the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
8.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between
62,6
°
F
~
86
°
F
In auto mode, the machine will choose cooling,
heating or fan-only mode according to ΔT (ΔT
=T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
35,6 ºF
Cooling
28
≤ΔT≤
35,6 ºF
Fan-only
ΔT<
28
ºF
Heating
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for 15 minutes and then choose mode
according to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
8.4.5 Drying mode
Indoor fan speed is fixed at breeze and can’t be
changed. The louver angle is the same as in
cooling mode.
All protections are active and the same as that
in cooling mode.
8.4.6 Forced operation function
Forced cooling mode:
The compressor and outdoor fan keep running
and the indoor fan runs at low speed. After
running for 30 minutes, AC will turn to auto
mode with
75,2ºF
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal auto mode with
75,2ºF
setting
temperature.
When AC receives signals, such as switch on,
switch off, timer on, timer off, mode setting, fan
speed setting, sleeping mode setting, follow me
setting, it will quit the forced operation.
8.4.7
Sleep function
8.4.7.1 The sleep function is available in
cooling, heating or auto mode.
8.4.7.2. Operation process in sleep mode is as
follow:
When cooling, the setting temperature rises
33,8ºF
(be lower than
86ºF
) every one hour,
2 hours later the setting temperature stops
rising and the indoor fan is fixed at low speed.
When
heating,
the
setting
temperature
decreases
33,8ºF
(be higher than
62,6ºF
)
every one hour, 2 hours later the setting
temperature stops rising and indoor fan is fixed
at low speed. (Anti-cold wind function has the
priority). 8.4.7.3 Operation time in sleep mode
is 7 hours. After 7 hours the AC quits this mode
and turns off.
8.4.7.4 Timer setting is available
8.4.8 Auto-Restart function
The indoor unit is equipped with auto-restart
function, which is carried out through an
auto-restart module. In case of a sudden power
failure, the module memorizes the setting
conditions before the power failure. The unit will
resume the previous operation setting (not
including swing function) automatically after 3
minutes when power returns.
If the memorization condition is forced cooling
mode, the unit will run in cooling mode for 30
minutes and turn to auto mode as
75,2ºF
setting temp.