9.3.6 Refrigerant Leakage Detection diagnosis and solution(EC)
Error Code
EC
Malfunction decision
conditions
Define the evaporator coil temp.T2 of the compressor just starts
running as Tcool.
In the beginning 8 minutes after the compressor starts up, if T2
<
Tcool
-
1
℃
(Tcool
-
33.8
°F) does not keep continuous 4
seconds and compressor running frequency higher than 50Hz
does not keep continuous 3 minutes, and this situation happens
3 times, the display area will show “EC” and AC will turn off.
Supposed causes
●
T2 sensor faulty
●
Indoor PCB faulty
●
System problems, such as leakage or blocking.
Trouble shooting: