830.013.02.K_Installation Guidelines (USA ONLY!) - cBoxX (Version 1.3).docx
8 | P a g e
3.0 Technical Requirements
3.1 Glycol
The cBoxX chillers require a water/ glycol mixture of 35-37 percent glycol to water for regions
with ambient temperatures > -13F (-25C). Regions with colder temperatures require a low
ambient chiller model and higher glycol concentrations (up to 50%).
KKT recommends using Distilled, Demineralized or Reverse Osmosis water
Allowed Glycol: Ethylene
Prohibited
:
Do not use automotive anti-freeze, or mixture containing >50% concentration of glycol.
DO not mix different brands or types of glycol without approval from the factory.
Tap water should not be used.
Required Volume
Piping Calculations:
Pipe size:
2-1/2”
= 2.43 Gal/Ft. (2,8 ltr/mtr)
Pipe size:
2“
= 1.74 Gal/Ft. (2,0 ltr/mtr)
Pipe size:
1-1/2”
= 1.04 Gal/Ft. (1,2 ltr/mtr)
Volume needed for the chiller is 13 gal. (50 l).
Take into consideration the amount of required glycol within the Healthcare application itself.
3.2 Air Vents:
Please ensure that air vents are placed at the highest point of the water loop in supply and
return line.
Example of automatic air vent:
KKT#
:
654936
Description:
Air vent - EA122A1002
Price:
$30.00 USD +S&H