APPENDIX B: KISTLER-MORSE
®
PROTOCOL SERIAL COMMANDS
‘wg’ Command — Write Setpoint State
This command is sent by the master to set the setpoint state of an STXplus. This can only be
accomplished if setpoint test is enabled (see command “GB/PB“). Acceptable values for setpoint
number is 1 and 2. The range of acceptable values is 0-1 where 0 is setpoint off or 1 is setpoint
on. For this example, the master sets setpoint 1’s state for an STXplus at address 01 to 1
(setpoint on). Any of the 6 leading zeros may be omitted.
Request from Master
Response from STXplus
>aawgn000000dssr
Ar
Format
>01wg11A1r
Ar
Example
‘GB’ Command — Read Setpoint Test Mode
This command is sent by the master to request the STXplus to send the setpoint test mode.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where
0 is test mode disabled or 1 is test mode enabled. The default value is 1 (test mode enabled).
For this example, the master requests setpoint 2’s test mode for an STXplus at address 01 which
returns 0 (test mode disabled) and a checksum of 50.
Request from Master
Response from STXplus
>aaGTnssr
A000000dssr
Format
>01GB21Cr
A000000050r
Example
‘PB’ Command — Write Setpoint Test Mode
This command is sent by the master to set the setpoint test mode of an STXplus. Acceptable
values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where 0 is test mode
disabled or 1 is test mode enabled. For this example, the master sets setpoint 1’s state for an
STXplus at address 01 to 1 (test mode enabled). Any of the 6 leading zeros may be omitted.
Request from Master
Response from STXplus
>aaPBn000000dssr
Ar
Format
>01PB1155r
Ar
Example
‘GH’ Command — Read Setpoint Value
This command is sent by the master to request the STXplus to send the setpoint value.
Acceptable values for setpoint number is 1 and 2. The range of this value can be ±2,147,483,647.
The default value is 0. For this example, the master requests setpoint 1’s value for an STXplus at
address 01 assuming it is using a format of 4(X.XX), which returns 347.51 engineering units and
a checksum of 32.
Request from Master
Response from STXplus
>aaGHnssr
A(-)ffffffffssr Format
>01GH121r
A347.5132r Example
B-26
Содержание STXplus
Страница 18: ...CHAPTER 3 STAND ALONE ANALOG CALIBRATION AND SET UP Table 3 2 3 9...
Страница 21: ...APPENDIX B KISTLER MORSE PROTOCOL SERIAL COMMANDS B 2...
Страница 22: ...APPENDIX B KISTLER MORSE PROTOCOL SERIAL COMMANDS B 3...
Страница 61: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS Table C 1 Modbus Address Map C 8...
Страница 62: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS C 9 Table C 1 Modbus Address Map continued...
Страница 63: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS Table C 1 Modbus Address Map continued C 10...
Страница 64: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS C 11 Table C 1 Modbus Address Map continued...
Страница 65: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS Table C 1 Modbus Address Map continued C 12...
Страница 67: ...APPENDIX D TECHNICAL DRAWINGS D 2...
Страница 68: ...APPENDIX D TECHNICAL DRAWINGS D 3...
Страница 69: ...APPENDIX D TECHNICAL DRAWINGS D 4...
Страница 70: ...APPENDIX D TECHNICAL DRAWINGS D 5...
Страница 71: ...APPENDIX D TECHNICAL DRAWINGS D 6...
Страница 72: ...APPENDIX D TECHNICAL DRAWINGS D 7...
Страница 74: ...NOTES...
Страница 75: ...NOTES...