APPENDIX B: KISTLER-MORSE
®
PROTOCOL SERIAL COMMANDS
Request from Master
Response from STXplus
>aaK2ssr
A000000dssr
Format
>01K2DEr
A000000050r
Example
‘L2’ Command — Write AB-RIO Baud Rate
This command is sent by the master to set the AB-RIO baud rate of an STXplus. The range of
acceptable values is 0-2 where 0 for 57.6K, 1 for 115.2K, or 2 for 230.4K. For this example, the
master sets AB-RIO baud rate for an STXplus at address 01 to 1 (115.2K). Any of the 6 leading
zeros may be omitted.
Request from Master
Response from STXplus
>aaL2000000dssr
Ar
Format
>01L2110r
Ar
Example
‘K3’ Command — Read AB-RIO Address
This command is sent by the master to request the STXplus to send the AB-RIO address. The
range of acceptable values is 0-255. For this example, the master requests AB-RIO address for
an STXplus at address 01 which returns 57 and a checksum of 5C.
Request from Master
Response from STXplus
>aaK3ssr
A0000dddssr
Format
>01K3DFr
A00000575Cr
Example
‘L3’ Command — Write AB-RIO Address
This command is sent by the master to set the AB-RIO address of an STXplus. The range of
acceptable values is 0-255. For this example, the master sets AB-RIO address for an STXplus at
address 01 to 12. Any of the leading zeros may be omitted.
Request from Master
Response from STXplus
>aaL30000dddssr
Ar
Format
>01L31243r
Ar
Example
‘K4’ Command — Read AB-RIO Group
This command is sent by the master to request the STXplus to send the AB-RIO group. The
range of acceptable values is 0-3 where 0 for Group 0, 1 for Group 2, 2 for Group 4, or 3 for
Group 6. For this example, the master requests AB-RIO group for an STXplus at address 01
which returns 3 (Group 6) and a checksum of 53.
Request from Master
Response from STXplus
>aaK4ssr
A000000dssr
Format
>01K4DEr
A000000353r
Example
‘L4’ Command — Write AB-RIO group
This command is sent by the master to set the AB-RIO group of an STXplus. The range of
acceptable values is 0-3 where 0 for Group 0, 1 for Group 2, 2 for Group 4, or 3 for Group 6. For
this example, the master sets AB-RIO group for an STXplus at address 01 to 1 (Group 2). Any of
the 6 leading zeros may be omitted.
B-29
Содержание STXplus
Страница 18: ...CHAPTER 3 STAND ALONE ANALOG CALIBRATION AND SET UP Table 3 2 3 9...
Страница 21: ...APPENDIX B KISTLER MORSE PROTOCOL SERIAL COMMANDS B 2...
Страница 22: ...APPENDIX B KISTLER MORSE PROTOCOL SERIAL COMMANDS B 3...
Страница 61: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS Table C 1 Modbus Address Map C 8...
Страница 62: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS C 9 Table C 1 Modbus Address Map continued...
Страница 63: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS Table C 1 Modbus Address Map continued C 10...
Страница 64: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS C 11 Table C 1 Modbus Address Map continued...
Страница 65: ...APPENDIX C MODBUS PROTOCOL SERIAL COMMANDS Table C 1 Modbus Address Map continued C 12...
Страница 67: ...APPENDIX D TECHNICAL DRAWINGS D 2...
Страница 68: ...APPENDIX D TECHNICAL DRAWINGS D 3...
Страница 69: ...APPENDIX D TECHNICAL DRAWINGS D 4...
Страница 70: ...APPENDIX D TECHNICAL DRAWINGS D 5...
Страница 71: ...APPENDIX D TECHNICAL DRAWINGS D 6...
Страница 72: ...APPENDIX D TECHNICAL DRAWINGS D 7...
Страница 74: ...NOTES...
Страница 75: ...NOTES...