15
disconnect all appliances disconnected immediately and have them inspected by a qualified electrician
before attempting to use them again.
Do not attempt to operate appliances if the ground fault circuit interrupter reset
button pops out repeatedly during use.
Only the ground fault circuit interrupter receptacle provides ground fault protection.
5,3 Voltage Selection Switch
The voltage selection switch has two positions: AC120V and AC120/240V.
1. When the voltage selection switch is in the 120/240V position, the generator supplies both 120V and
240V AC power. If you operate the generator with the switch in this position, the electric current is
limited to 15 amps to the 120V receptacles although it can provide 15 amps at 240V from the
120/240V receptacle.
2. When the voltage selection switch in the 120V position, the generator supplies 120V AC only. It can
supply a full 30 amps to the 30 Amp receptacle or 20A to the GFCI receptacle. Total current is limited
to 33 amps at rated load.
5.4 AC Operation
1. Start the engine and make sure the green output indicator light comes on.
2. Confirm that the appliance to be used is switched off then plug in the appliance.