 Versions: V2.1.060721. Parameters: 97C1i,103F1i, 109C2i,115F2i 

*!!*

 

 
 

 

Made in Greece 

 

 

ATTENTION

: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such a way that it 

cannot be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power supply of the device before 

proceeding to any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. Prevent electrostatic discharges 
and sharp objects from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with 

the power supply cables. 
The device is under two year

s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized 

technician. The guarantee covers only the replacement or the service of the device. 

 preserves the right to adjust its products without further notice.

 

 

 

 

392 Mesogeion Avenue Agia Paraskevi 153 41 Τ: 210 6533730 F: 210 6546331  [email protected]  www.kiour.com

 

V2.1.080721

 

 

Содержание MACON HP

Страница 1: ...an monitor all temperatures compressors relays alarms parameters while sending SMS and emails in case of an alarm More than 250 devices can connect to this network Connect to a Remote Control device it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device It can be installed up to 500 meters away from the main device PARAMETERS Para...

Страница 2: ...mpressor C2b operation hours hours A15 Hs1 out of order A16 Hs2 out of order 1 SCo SET POINT of compressor in Cooling mode LCL LCH 10 C 2 SHt SET POINT of compressor in Heating mode LHL LHH 20 C 3 Cod Access code with Cod 22 we access all the following parameters 0 255 0 4 diS Adjust which sensor is displayed on screen where 1 sensor 1 etc 1 5 1 5 rCo Differential of SET POINT in Cooling mode 0 1 ...

Страница 3: ...t Point rH1 Below Set Point resistance is ON 0 1 1 units 39 rC1 activation deactivation of the cooling resistance ON based on Set Point rSC Below Set Point resistance is ON 5 C 0 1 1 units 40 rSC Resistance Set Point Cooling Below Set Point resistance is ON 5 C Works with T2 T4 50 150 15 0 C 41 SE1 out of order 0 1 1 units 42 SE2 Sensor activation Νο 2 where 0 sensor deactivated 1 sensor activated...

Страница 4: ...circuits Values 1 One circuit 2 Two circuits 1 2 2 units 86 GLE out of order 0 255 0 87 GPo Compressor boot time in Power Up 0 200 0 sec 88 GLC Value 0 gives priority to the compressor with the fewest hours 1 gives constant priority to the compressor 1 2 gives constant priority to the compressor 2 0 2 0 units 89 GFP Pump operation with ALARM safety thermostat in OFF machine condition 0 the pump is...

Страница 5: ... and C2b relays Value 0 ON the relay on the thermostat ON Value 1 OFF the relay on the thermostat ON 0 1 0 units 124 LPA ALARM Operation of Low Pressure when the compressor is OFF Value 0 Blocks ALARM Value 1 ALARM is free 0 1 1 units ALARM TABLE Display flashes when the alarm messages are displayed 1 HP1 ALARM HIGH PRESSURE C1 Stops the operation of compressor C1 By adjusting parameter GAL 0 alar...

Страница 6: ...P2 Drainage procedure of the 2nd circuit after deFrost 3 dF1 dFrost is running on the 1st circuit 4 dF2 dFrost is running on the 2nd circuit On the MACON_HPB the flashing LED in position No 2 indicates that the device is communicating with the main unit The LED in position of terminal No 11 indicates that the device is under voltage The same applies to compressor C2 respectively with parameters C2...

Страница 7: ...The same applies to FAN 2 respectively with the parameters F2d F2U F2C ...

Страница 8: ... sensor No 1 Water inlet circuit 1 Thermostat operation HEATING COOLING Temperature sensor No 2 Water outlet Safety thermostat No 1 Resistance No 1 Temperature sensor No 3 deFrost control Temperature sensor No 4 Water outlet circuit 2 Safety thermostat No 2 Resistance No 2 Temperature sensor No 5 Defrost control C2 ...

Страница 9: ...g magnets in areas affected by direct sunlight or rain Prevent electrostatic discharges and sharp objects from been inserted to the device Separate signal cables from power supply cables to prevent electromagnetic disorders Signal cables must never be in the same pipe with the power supply cables The device is under two year s guarantee The guarantee is valid only if the manual instructions have b...