DISPLAY AND RESET OPERATION HOUR OF COMPRESSORS
Press
to display the first parameter
SCo
. By pressing up arrow button
parameters from A16 to A1 are displayed.
From A10-A14 are the operating hours of
compressors and pump. When the parameter name is displayed, for eg.
h P
and press
SET
the pump operating hours are displayed and by pressing simultaneously
+
resets the hours. Then, press
to
confirm
the nihilism. When the operating hours indicator flashes, it means that the hours are 100.
DISPLAY TEMPERATURE and 4-20 mA
Parameters from A1 to A9: by pressing
SET
displays the temperature of the corresponding sensor or 4-20 mA as described in the parameter table.
LED OPERATION
ON
The system is activated.
C1
ON when the compressor
C1
operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed.
C1b
ON when the compressor
C1b
operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed.
C2
ON when the compressor
C2
operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed.
C2b
ON when the compressor
C2b
operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed.
C
Cool – indication that system operates in cooling mode.
H
Heat – indication that system operated in heating mode.
Blinks if an alarm is active.
RESET TO FACTORY DEFAULT SETTINGS
Enter the parameter
Cod = 31
and press it twice to enter the factory values of the parameters (see in the following table the column default values).
TABLE 1
No
PARAMETERS
DESCRIPTION
min
max
DEFAULT
UoM.
Α1
t1
Temperature sensor Νo 1 (Input)
-
-
-
°C
Α2
t2
Temperature sensor Νo 2 (Water output 1)
-
-
-
°C
Α3
t3
Temperature sensor Νο 3 (deFrost C1)
-
-
-
°C
Α4
HP1
High pressure, circuit 1. HP1
-
-
-
pressure
Α5
LP1
out of order
-
-
-
pressure
Α6
t4
Temperature sensor Νο 4 (Water output 2)
-
-
-
°C
Α7
t5
Temperature sensor Νο 5 (deFrost C2 )
-
-
-
°C
Α8
HP2
High pressure, circuit 2. HP2
-
-
-
pressure
A9
LP2
out of order
-
-
-
pressure
A10
h P
Pump operation hours
Operation hours:
When the symbol
x100
is ON, the
operation hours are x100.
To reset the timer, press simultaneously
+
and
then
.
-
-
-
hours
A11
h 1
Compressor C1 operation hours
-
-
-
hours
A12
h1b
Compressor C1b operation hours
-
-
-
hours
A13
h2
Compressor C2 operation hours
-
-
-
hours
A14
h2b
Compressor C2b operation hours
-
-
-
hours
A15
Hs1
out of order
-
-
-
-
A16
Hs2
out of order
-
-
-
-
1
SCo
SET POINT of compressor in Cooling mode
LCL
LCH
10
°C
2
SHt
SET POINT of compressor in Heating mode
LHL
LHH
20
°C
3
Cod
Access code: with
Cod=22
we access all the following parameters
0
255
0
-
4
diS
Adjust which sensor is displayed on screen, where 1 = sensor 1, etc.
1
5
1
-
5
rCo
Differential of SET POINT in Cooling mode
0.1
25
1
°C
6
rHt
Differential of SET POINT in Heating mode
0.1
25
1
°C
7
rS2
Differential of the second SET POINT
The differential is divided into 4 parts. E.g. for
rS2 = 4
and
SCo = 10
. In the 1
st
circuit the 1
st
ON at
10°C the second ON at 11°C (TADEM). The 3
rd
of the 2
nd
circuit, ON at 12°C and the 4
th
ON at
13°C (TADEM). In circuits with a compressor / circuit, the 1
st
of the 1
st
ON circuit at 10°C and the
2
nd
of the 2
nd
ON circuit at 12°C.
0.1
25,0
2,0
°C
8
LCL
minimum temperature limit of SCo in Cooling mode
-50
150
-10,0
°C
9
LCH
maximum temperature limit of SCo in Cooling mode
-50
150
40,0
°C
10
LHL
minimum temperature limit of SHt in Heating mode
-50
150
10,0
°C
11
LHH
maximum temperature limit of SHt in Heating mode
-50
150
60,0
°C
12
FoP
Fan operation
0 =
Fans are always OFF
1 =
Fans are ΟΝ when the device is ΟΝ.
2 =
Fan is ON when the corresponding compressor is ON
3 =
The fans operate on the basis of SET POINT.
FSC
in cooling and
FSH
in heating.
The fan is controlled by the defrost temperature/pressure. The fan is ON when the temperature /
pressure of the defrost sensor commands the fan to ON (in normal operation and not in defrost
process). When OFF the OFF compressor and the fan
0
3
1
units
13
FSC
SET POINT of fan in Cooling mode. Operates when parameter
FoP=3.
The differential is constant equal to 1,0 °C.
-50
150
15,7
°C
14
FSH
SET POINT of fan in Heating mode. Operates when parameter
FoP=3
.
The differential is constant equal to 1,0 °C.
-50
150
15,7
°C
15
doP
Defrost operation, where
0 =
defrost operation is deactivated and
1 =
defrost operation is activated
0
1
1
units
16
dto
0 =
defrost ends based only on parameter timer
dt3
1 =
defrost ends when the temperature reaches temperature end deFrost. In the meantime, if timer
dt3
elapses, defrost ends and an indication
dF
appears on screen for a few seconds.
0
1
1
units
17
dbE
Temperature starting defrost
When the temperature is below the
dbE
limit continuously for a time longer than the
dt1
time and with
the compressor ON, then a defrost process starts.
With the parameter
t3E = 1
it works as a SET POINT for safety thermostat of temperature
SEn3
,
SE55
-50
150
3.6
°C