KIOUR MACON HP Скачать руководство пользователя страница 2

 

DISPLAY AND RESET OPERATION HOUR OF COMPRESSORS 

Press 

 to display the first parameter 

SCo

. By pressing up arrow button

 parameters from A16 to A1 are displayed. 

 

From A10-A14 are the operating hours of 

compressors and pump. When the parameter name is displayed, for eg. 

h P

 and press 

SET

 the pump operating hours are displayed and by pressing simultaneously 

 

 resets the hours. Then, press 

  to 

confirm

 the nihilism. When the operating hours indicator flashes, it means that the hours are 100.  

DISPLAY TEMPERATURE and 4-20 mA 

Parameters from A1 to A9: by pressing 

SET

 displays the temperature of the corresponding sensor or 4-20 mA as described in the parameter table. 

LED OPERATION 
ON

 

The system is activated. 

C1             

ON when the compressor 

C1

 operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed. 

C1b

           ON when the compressor 

C1b

 operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed. 

C2             

ON when the compressor 

C2

 operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed.

 

 

C2b

           ON when the compressor 

C2b

 operates. When it starts blinking then the compressor is set to ON but a timer is active and waits to elapsed. 

C

                Cool – indication that system operates in cooling mode. 

H

                Heat – indication that system operated in heating mode. 

         

Blinks if an alarm is active. 

RESET TO FACTORY DEFAULT SETTINGS 

Enter the parameter 

Cod = 31

 and press it twice to enter the factory values of the parameters (see in the following table the column default values).

 

TABLE 1 

 

 

 

 

No 

PARAMETERS 

DESCRIPTION 

min 

max 

DEFAULT 

UoM. 

Α1 

t1 

Temperature sensor Νo 1 (Input) 

°C 

Α2 

t2 

Temperature sensor Νo 2 (Water output 1) 

°C 

Α3 

t3 

Temperature sensor Νο 3 (deFrost C1) 

°C 

Α4 

HP1 

High pressure, circuit 1. HP1 

pressure

 

Α5 

LP1 

out of order 

pressure 

Α6 

t4 

Temperature sensor Νο 4 (Water output 2) 

°C 

Α7 

t5 

Temperature sensor Νο 5 (deFrost C2 ) 

°C 

Α8 

HP2 

High pressure, circuit 2. HP2

 

pressure

 

A9 

LP2 

out of order

 

pressure

 

A10 

h P 

Pump operation hours 

Operation  hours: 

When  the  symbol 

x100

  is  ON,  the 

operation hours are x100.  
To reset the timer, press simultaneously  

 

+

 

and 

then 

.

 

-

 

-

 

-

 

hours 

A11 

h 1 

Compressor C1 operation hours 

-

 

-

 

-

 

hours 

A12 

h1b 

Compressor C1b operation hours 

hours 

A13 

h2 

Compressor C2 operation hours 

hours 

A14 

h2b 

Compressor C2b operation hours 

 

-

 

-

 

hours 

A15 

Hs1 

out of order 

-

 

-

 

A16 

Hs2 

out of order 

-

 

-

 

SCo 

SET POINT of compressor in Cooling mode 

 

LCL

 

LCH

 

10 

°C 

SHt 

SET POINT of compressor in Heating mode

 

LHL

 

LHH

 

20 

°C 

Cod 

Access code: with 

Cod=22

 we access all the following parameters 

255 

diS 

Adjust which sensor is displayed on screen, where 1 = sensor 1, etc.  

rCo 

Differential of SET POINT in Cooling mode 

0.1 

25 

°C 

rHt 

Differential of SET POINT in Heating mode 

0.1 

25 

°C 

rS2 

Differential of the second SET POINT 
 

The differential is divided into 4 parts. E.g. for 

rS2 = 4

 and 

SCo = 10

. In the 1

st

 circuit the 1

st

 ON at 

10°C the second ON at 11°C (TADEM). The 3

rd

 of the 2

nd

 circuit, ON at 12°C and the 4

th

 ON at 

13°C (TADEM). In circuits with a compressor / circuit, the 1

st

  of the 1

st

  ON circuit at 10°C and the 

2

nd

  of the 2

nd

  ON circuit at 12°C. 

0.1 

25,0 

2,0 

°C 

LCL 

minimum temperature limit of SCo in Cooling mode 

-50 

150 

-10,0 

°C 

LCH 

maximum temperature limit of SCo in Cooling mode

 

-50 

150 

40,0 

°C 

10 

LHL 

minimum temperature limit of SHt in Heating mode

 

-50 

150 

10,0 

°C 

11 

LHH 

maximum temperature limit of SHt in Heating mode 

-50 

150 

60,0 

°C 

12 

FoP 

Fan operation

 

0 =

 Fans are always OFF 

1 =

 Fans are ΟΝ when the device is ΟΝ. 

2 =

 Fan is ON when the corresponding compressor is ON 

3 =

 The fans operate on the basis of SET POINT. 

FSC

 in cooling and 

FSH

 in heating.  

The fan is controlled by the defrost temperature/pressure. The fan is ON when the temperature / 
pressure of the defrost sensor commands the fan to ON (in normal operation and not in defrost 
process). When OFF the OFF compressor and the fan

 

units 

13 

FSC 

SET POINT of fan in Cooling mode. Operates when parameter 

FoP=3. 

The differential is constant equal to 1,0 °C. 

-50 

150 

15,7 

°C 

14 

FSH 

SET POINT of fan in Heating mode. Operates when parameter 

FoP=3

.

  

The differential is constant equal to 1,0 °C.

 

-50 

150 

15,7 

°C 

15 

doP 

Defrost operation, where 

0 =

 defrost operation is deactivated and 

1 =

 defrost operation is activated

 

units 

16 

dto 

0 =

 defrost ends based only on parameter timer 

dt3

 

1 =

 defrost ends when the temperature reaches temperature end deFrost. In the meantime, if timer 

dt3 

elapses, defrost ends and an indication 

dF

 appears on screen for a few seconds.

 

units 

17 

dbE 

Temperature starting defrost

 

When the temperature is below the 

dbE

 limit continuously for a time longer than the 

dt1

 time and with 

the compressor ON, then a defrost process starts. 
With the parameter 

t3E = 1

 it works as a SET POINT for safety thermostat of temperature 

SEn3

SE55

 

-50 

150 

3.6 

°C 

Содержание MACON HP

Страница 1: ...an monitor all temperatures compressors relays alarms parameters while sending SMS and emails in case of an alarm More than 250 devices can connect to this network Connect to a Remote Control device it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device It can be installed up to 500 meters away from the main device PARAMETERS Para...

Страница 2: ...mpressor C2b operation hours hours A15 Hs1 out of order A16 Hs2 out of order 1 SCo SET POINT of compressor in Cooling mode LCL LCH 10 C 2 SHt SET POINT of compressor in Heating mode LHL LHH 20 C 3 Cod Access code with Cod 22 we access all the following parameters 0 255 0 4 diS Adjust which sensor is displayed on screen where 1 sensor 1 etc 1 5 1 5 rCo Differential of SET POINT in Cooling mode 0 1 ...

Страница 3: ...t Point rH1 Below Set Point resistance is ON 0 1 1 units 39 rC1 activation deactivation of the cooling resistance ON based on Set Point rSC Below Set Point resistance is ON 5 C 0 1 1 units 40 rSC Resistance Set Point Cooling Below Set Point resistance is ON 5 C Works with T2 T4 50 150 15 0 C 41 SE1 out of order 0 1 1 units 42 SE2 Sensor activation Νο 2 where 0 sensor deactivated 1 sensor activated...

Страница 4: ...circuits Values 1 One circuit 2 Two circuits 1 2 2 units 86 GLE out of order 0 255 0 87 GPo Compressor boot time in Power Up 0 200 0 sec 88 GLC Value 0 gives priority to the compressor with the fewest hours 1 gives constant priority to the compressor 1 2 gives constant priority to the compressor 2 0 2 0 units 89 GFP Pump operation with ALARM safety thermostat in OFF machine condition 0 the pump is...

Страница 5: ... and C2b relays Value 0 ON the relay on the thermostat ON Value 1 OFF the relay on the thermostat ON 0 1 0 units 124 LPA ALARM Operation of Low Pressure when the compressor is OFF Value 0 Blocks ALARM Value 1 ALARM is free 0 1 1 units ALARM TABLE Display flashes when the alarm messages are displayed 1 HP1 ALARM HIGH PRESSURE C1 Stops the operation of compressor C1 By adjusting parameter GAL 0 alar...

Страница 6: ...P2 Drainage procedure of the 2nd circuit after deFrost 3 dF1 dFrost is running on the 1st circuit 4 dF2 dFrost is running on the 2nd circuit On the MACON_HPB the flashing LED in position No 2 indicates that the device is communicating with the main unit The LED in position of terminal No 11 indicates that the device is under voltage The same applies to compressor C2 respectively with parameters C2...

Страница 7: ...The same applies to FAN 2 respectively with the parameters F2d F2U F2C ...

Страница 8: ... sensor No 1 Water inlet circuit 1 Thermostat operation HEATING COOLING Temperature sensor No 2 Water outlet Safety thermostat No 1 Resistance No 1 Temperature sensor No 3 deFrost control Temperature sensor No 4 Water outlet circuit 2 Safety thermostat No 2 Resistance No 2 Temperature sensor No 5 Defrost control C2 ...

Страница 9: ...g magnets in areas affected by direct sunlight or rain Prevent electrostatic discharges and sharp objects from been inserted to the device Separate signal cables from power supply cables to prevent electromagnetic disorders Signal cables must never be in the same pipe with the power supply cables The device is under two year s guarantee The guarantee is valid only if the manual instructions have b...