KIOUR MACON HP Скачать руководство пользователя страница 4

No

 

PARAMETERS

 

DESCRIPTION

 

min

 

max

 

DEFAULT

 

UoM

 

62 

tPC 

Pump-Compressor

 Time. Compressor start time after pump. 

200 

sec 

63 

tCP 

Compressor-Pump 

Time. OFF time of the pump after OFF of the compressor.

 

200 

min 

64 

tPO 

 Intermittent  operation  of  the  pump  when  the  compressor  is  OFF.  The 

tPO

  parameter  works  in 

conjunction with the 

GFr

 parameter. 

GFr = 0

 deactivates the function of the 

tPO

 parameter.  

If 

GFr = 1

 and 

tPO = 1-100 min

, the pump restarts after the time specified by the parameter (OFF 

time) and remains ON at the time specified by the parameter 

tPd,

 (time ON). 

100 

min 

65 

tPd 

 It works in conjunction with the 

tPO

 parameter and sets the operating time of the pump 

100 

min 

66 

tF1 

Bypass time of 

FLOW SWITCH

 at pump start 

200 

sec 

67 

tF2 

Bypass time of 

FLOW SWITCH

 during operation 

200 

sec 

68 

too 

Time from ON to ON of the same compressor, where 1 unit = 10 sec  

200 

10sec 

69 

tFo 

Time from OFF to ON of the same compressor, where 1 unit = 10 sec 

 

200 

10sec 

70 

tdC 

Time from ON to ON between the two compressors

 

200 

sec 

72 

tFC 

Time from OFF to OFF between the two compressors 

200

 

sec

 

73 

ton 

Minimum compressor operating time 

200 

sec 

74 

tLP 

Bypass time of low compressor pressure 

(LP1, LP2)

 at start-up

 

200 

sec 

75 

tLo 

Bypass time of low compressor pressure 

(LP1, LP2)

 during operation

 

200 

sec 

76 

tAF 

Safety thermostat bypass time at startup

 

200 

30 

sec 

77 

ttA 

In TANDEM mode

. Switch compressors if only one works for 

time > ttA 

100 

30 

min 

78 

Grc 

ON-OFF 

Remote Control of the system. 

 Value 

= 1

 Input enabled. Value 

= 0

 the keyboard of the device is activated. 

 

units 

79 

GrH 

Remote Control of 

HEAT-COOL

 selection of the system.  

Value 

= 1

 Input enabled. Value 

= 0

 the device keyboard is activated.

 

units 

80 

itY 

Instrument Type:

 

1 = 

TADEM, 

2 = 

CAPACITIVE, 

3 =

 one compressor / circuit.

 

units 

81 

C12 

Common circuit (condenser). 
Value 

= 1

=> 1

st

 condenser, Value 

= 2 

=> 2

nd

 condenser. With a 

common

 condenser, if FAN1 is ON 

then the FAN2 is ON. If FAN2 is ON then the FAN1 is ON.  The parameter only affects the fans. 

units 

82 

GAL 

Alarm function, automatic or manual,

 

Value: 

0 =

 alarms manual Reset: HP1, LP1, PH1, Safety Thermostat 1, FLOW             

SWITCH, HP2, LP2, PH2, Safety Thermostat 2 

 

1 =

  automatic Reset 

units 

83 

GSu 

Valve Inversion Parameter  

Value: 

0 =

 In Cooling the valve relays are OFF and in heating ON 

 

1 =

 In Heating the valve relays are OFF and in Cooling ON

 

units 

84 

GFr 

Value:  

0

The pump is running continuously.

 

                 1= 

The pump starts and stops with the compressors, based on the 

tPC 

and 

tCP

 times.

 

units 

85 

Gnc 

Number of circuits, Values:  

1 =

 One circuit,  

2 =

 Two circuits   

 

units 

86 

GLE

 

out of order

 

0

 

255

 

0

 

-

 

87 

GPo 

Compressor boot time in Power Up 

0

 

200

 

0

 

sec

 

88 

GLC 

Value:      

0=

 gives priority to the compressor with the fewest hours 

                

1=

 gives constant priority to the compressor 1 

                

2=

 gives constant priority to the compressor 2

 

units 

89 

GFP 

Pump operation with ALARM safety thermostat in OFF machine condition.  
0 = 

the pump is

 deactivated

 when safety thermostat is activated  

1 =

 the pump is 

activated

 when safety thermostat is activated 

90 

trE 

Time response of the device on network

 

30 

100 

30 

units 

91 

Add

 

0 =

 network is deactivated. 

1=

 Remote Control operation is activated. 

Address of the device on network from 1 – 255 

255 

units

 

92 

nCo 

0 = 

SLAVE: PC operation 

1 = 

MASTER: REMOTE CONTROL operation and parameter 

Add

 = 1 

units

 

93 

C1d 

Lower  analog  output  voltage.  Compressor  C1  of  the  1st  circuit.  The  analog  signal  0-10  Volt 
corresponds consistently to C1. Values from 0 to 4.0 Volt. The analog output will be between 

C1U - 

C1d

 in a temperature range defined by parameter 

C1H

 or 

C1C

.  

For example, 

C1U - C1d = 7

 and 

C1H = 3

 and 

SHt = 45°C

, the voltage will change 

10-3 Volt

 from 

42 

÷ 45°C

 on heating (see figure 5B). 

3,0 

Volt

 

94 

C1U 

C1. Compressor C1 of the 1st circuit Higher voltage at the analog output. 

10 

10,0 

Volt 

95 

C1H 

C1. Compressor C1 of the 1st circuit.  

In the heating:

 Temperature range to which the proportional voltage at the output corresponds.

 

1.0 

25.0 

3.0 

°C 

96 

C1C 

C1. Compressor C1 of the 1st circuit.  

In the cooling:

 Temperature range to which the proportional voltage at the output corresponds.

 

1.0 

25.0 

3.0 

°C 

97 

C1i

 

C1. Reverse analog signal at the output

 

units 

98 

C1A 

C1. Compressor C1 of the 1st circuit Increasing the value reduces the oscillation of the signal 0-10 
Volt. 

1

 

40

 

5

 

units

 

99 

F1d 

FAN 1. Lower analog output voltage. 1st circuit. Values from 0 to 4.0 Volt. The analog output will be 
between 

F1U - F1d

 in a temperature range defined by parameter 

F1H

 or 

F1C

. For, example 

F1U - 

F1d = 7

 and 

F1H = 3

 and 

SHt = 45 °C

, the voltage will change 

10-3 Volts

 from 

42 ÷ 45 °C

 on heating 

(see figure 6B). When the relays 

C1, C1b

 are OFF then the analog output is zero  

In the DRIPING_TIME phase it produces the maximum voltage 

3,0 

Volt 

100 

F1U 

FAN 1. Higher voltage at the analog output.  
When the relay of FAN 1 is OFF then the analog output is 0 Volt 

10 

10,0 

Volt 

101 

F1H 

FAN 1. In the heating. 
Temperature / pressure range to which the analog output voltage corresponds.

 

1.0 

25.0 

3.0 

°C 

102 

F1C 

FAN 1. In the cooling. 
Temperature / pressure range to which the analog output voltage corresponds.

 

1.0 

25.0 

3.0 

°C 

103 

F1i

 

FAN 1. Reverse analog signal at the output

 

units 

104 

F1A 

FAN 1. Increasing the value reduces the oscillation of the 0-10 Volt signal 

1

 

40

 

5

 

units

 

Содержание MACON HP

Страница 1: ...an monitor all temperatures compressors relays alarms parameters while sending SMS and emails in case of an alarm More than 250 devices can connect to this network Connect to a Remote Control device it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device It can be installed up to 500 meters away from the main device PARAMETERS Para...

Страница 2: ...mpressor C2b operation hours hours A15 Hs1 out of order A16 Hs2 out of order 1 SCo SET POINT of compressor in Cooling mode LCL LCH 10 C 2 SHt SET POINT of compressor in Heating mode LHL LHH 20 C 3 Cod Access code with Cod 22 we access all the following parameters 0 255 0 4 diS Adjust which sensor is displayed on screen where 1 sensor 1 etc 1 5 1 5 rCo Differential of SET POINT in Cooling mode 0 1 ...

Страница 3: ...t Point rH1 Below Set Point resistance is ON 0 1 1 units 39 rC1 activation deactivation of the cooling resistance ON based on Set Point rSC Below Set Point resistance is ON 5 C 0 1 1 units 40 rSC Resistance Set Point Cooling Below Set Point resistance is ON 5 C Works with T2 T4 50 150 15 0 C 41 SE1 out of order 0 1 1 units 42 SE2 Sensor activation Νο 2 where 0 sensor deactivated 1 sensor activated...

Страница 4: ...circuits Values 1 One circuit 2 Two circuits 1 2 2 units 86 GLE out of order 0 255 0 87 GPo Compressor boot time in Power Up 0 200 0 sec 88 GLC Value 0 gives priority to the compressor with the fewest hours 1 gives constant priority to the compressor 1 2 gives constant priority to the compressor 2 0 2 0 units 89 GFP Pump operation with ALARM safety thermostat in OFF machine condition 0 the pump is...

Страница 5: ... and C2b relays Value 0 ON the relay on the thermostat ON Value 1 OFF the relay on the thermostat ON 0 1 0 units 124 LPA ALARM Operation of Low Pressure when the compressor is OFF Value 0 Blocks ALARM Value 1 ALARM is free 0 1 1 units ALARM TABLE Display flashes when the alarm messages are displayed 1 HP1 ALARM HIGH PRESSURE C1 Stops the operation of compressor C1 By adjusting parameter GAL 0 alar...

Страница 6: ...P2 Drainage procedure of the 2nd circuit after deFrost 3 dF1 dFrost is running on the 1st circuit 4 dF2 dFrost is running on the 2nd circuit On the MACON_HPB the flashing LED in position No 2 indicates that the device is communicating with the main unit The LED in position of terminal No 11 indicates that the device is under voltage The same applies to compressor C2 respectively with parameters C2...

Страница 7: ...The same applies to FAN 2 respectively with the parameters F2d F2U F2C ...

Страница 8: ... sensor No 1 Water inlet circuit 1 Thermostat operation HEATING COOLING Temperature sensor No 2 Water outlet Safety thermostat No 1 Resistance No 1 Temperature sensor No 3 deFrost control Temperature sensor No 4 Water outlet circuit 2 Safety thermostat No 2 Resistance No 2 Temperature sensor No 5 Defrost control C2 ...

Страница 9: ...g magnets in areas affected by direct sunlight or rain Prevent electrostatic discharges and sharp objects from been inserted to the device Separate signal cables from power supply cables to prevent electromagnetic disorders Signal cables must never be in the same pipe with the power supply cables The device is under two year s guarantee The guarantee is valid only if the manual instructions have b...

Отзывы: