
No
PARAMETERS
DESCRIPTION
min
max
DEFAULT
UoM
105
C2d
C2. Lower analog output voltage. Compressor C2 of the 2
nd
circuit. The analog signal 0-10 Volt
corresponds consistently to C2. Values from 0 to 4.0 Volts. The analog output will be between
C2U -
C2d
in a temperature range defined by the parameter
C2H
or
C2C
. For example,
C2U - C2d = 7
and
C2H = 3
and
SHt =45°C
, the voltage will change
10-3Volt
from
42 ÷ 45°C
on heating (see
figure 5B).
0
5
3,0
Volt
106
C2U
C2. Higher voltage at the analog output.
6
10
10,0
Volt
107
C2H
C2. In the heating. Temperature / pressure range to which the analog output voltage corresponds.
1.0
25.0
3.0
°C
108
C2C
C2. In the cooling. Temperature / pressure range to which the analog output voltage corresponds.
1.0
25.0
3.0
°C
109
C2i
C2. Reverse analog signal at the output
0
1
0
units
110
C2A
C2. Increasing the value reduces the oscillation of the 0-10 Volt signal.
1
40
5
units
111
F2d
FAN 2. Lower analog output voltage. 2nd circuit. Values from 0 to 4.0 Volt. The analog output will
range between
F2U - F2d
in a temperature range defined by parameter
F2H
or
F2C
. For example,
F2U - F1d = 7
and
F2H = 3
and
SHt = 45 °C
, the voltage will change
10-3 Volt
from
42 ÷ 45 °C
on
heating (see figure 6B). When the relays
C2
,
C2b
are OFF then the analog output is zero.
In the DRIPING_TIME phase it produces the maximum voltage.
0
5
3,0
Volt
112
F2U
FAN 2. Higher voltage at the analog output.
When the relay of FAN 2 is OFF then the analog output is 0 Volt
6
10
10,0
Volt
113
F2H
FAN 2. In the heating.
Temperature / pressure range to which the analog output voltage corresponds.
1.0
25.0
3.0
°C
114
F2C
FAN 2. In the cooling.
Temperature / pressure range to which the analog output voltage corresponds.
1.0
25.0
3,0
°C
115
F2i
FAN2. Reverse analog signal at the output
0
1
0
units
116
F2A
FAN 2. Increasing the value reduces the oscillation of the 0-10 Volt signal
1
40
5
units
117
VtO
In case the machine is OFF. Time OFF of the valves after the minutes specified by the parameter
(See
EOV
parameter).
0
20
0
min
118
EOV
If
EOV = 0
and the system is OFF, then the valves are OFF after the time specified by parameter
VtO
.
If
EOV = 1
the valves remain in the state specified by the
GSu
parameter.
0
1
0
units
119
PrE
PREVENT
. In case the pressure of circuit 1 becomes higher than the value of the parameter, the
ALARM PREVENT
(Pr1)
is activated and turns OFF the 2
nd
compressor or CAPACITIVE of the 1st
circuit. The same applies to the second circuit. (
Pr2
). Activated if
PEn = 1
and with the parameters
SH1 = 1
and
SH2 = 1
respectively for circuit 1 and 2. With
itY = 3
(1 compressor / circuit) PREVENT
is deactivated.
PrE
Set Point works without differential.
5,0
99,9
40,0
units
120
HPA
In case the pressure of circuit 1 becomes higher than the value of the parameter, the high pressure
ALARM is activated by the transmitter (
P1H
), and turns OFF the compressors of the 1st circuit. The
same applies to the second circuit, called ALARM
P2H
. Activated if HEn = 1 and with the parameters
SH1 = 1
and
SH2 = 1
respectively for circuit 1 and 2.
The SET POINT of
HPA
works without differential.
5,0
99,9
40,0
units
121
PEn
Value
=0
Deactivate the parameter
PrE.
Value
=1
activate the
PrE
parameter.
0
1
0
units
122
HEn
Value
=0
Deactivate the parameter
HPA.
Value
=1
activate the
HPA
parameter.
0
1
0
units
123
CAV
Reverse operation of CAPACITIVE, C1b and C2b relays. Value
= 0
=> ON the relay on the thermostat
ON. Value
= 1
=> OFF the relay on the thermostat ON.
0
1
0
units
124
LPA
ALARM Operation of Low Pressure when the compressor is OFF.
Value
=0
=> Blocks ALARM. Value
= 1
=> ALARM is free
0
1
1
units
ALARM TABLE
Display flashes when the alarm messages are displayed
1
HP1
ALARM HIGH PRESSURE C1: Stops the operation of compressor C1. By adjusting parameter GAL = 0, alarm reset is manual.
2
LP1
ALARM LOW PRESSURE C1: Stops the operation of compressor C1. By adjusting parameter GAL = 0, alarm reset is manual.
3
C1
ALARM COMPRESSOR C1: Stops the operation of compressor C1. Alarm is only automatically deactivated when the cause of the alarm disappears.
4
FLS
ALARM FLOW SWITCH: ALARM from the FLOW SWITCH. By adjusting parameter GAL = 0, alarm reset is manual.
5
HP2
ALARM HIGH PRESSURE C2: Stops the operation of compressor C2. By adjusting parameter GAL = 0, alarm reset is manual.
6
LP2
ALARM LOW PRESSURE C2: Stops the operation of compressor C2. By adjusting parameter GAL = 0, alarm reset is manual.
7
C2
ALARM COMPRESSOR C2: Stops the operation of compressor C2. Alarm is only automatically deactivated when the cause of the alarm disappears.
8
Ar1
ALARM SENSOR 1: ALARM analog input Νο 1. Safety thermostat. (Water input). Sensor malfunction. Alarm is only automatically deactivated when the cause
of the alarm disappears.
9
Ar2
ALARM SENSOR 2: ALARM analog input Νο 2. Safety thermostat. (Water output). Circuit 1. Sensor malfunction. Alarm is only automatically deactivated
when the cause of the alarm disappears.
10
Ar3
ALARM SENSOR 3: ALARM analog input Νο 3. Defrost Sensor malfunction. Alarm is only automatically deactivated when the cause of the alarm disappears.
11
Ar4
ALARM SENSOR 4: ALARM analog input Νο 4. Safety thermostat. (Water output). Circuit 2. Sensor malfunction. Alarm is only automatically deactivated
when the cause of the alarm disappears.
12
Ar5
ALARM SENSOR 5: ALARM analog input Νο 5. Defrost. Sensor malfunction. Alarm is only automatically deactivated when the cause of the alarm disappears.
13
At1
ALARM FROST: ALARM from the Safety Thermostat Circuit 1. At compressor’s start-up, the thermostat is deactivated based on parameter timer tAF. By
adjusting GAL = 0, alarm reset is manual.
14
At2
ALARM FROST: ALARM from the Safety Thermostat Circuit 2. At compressor’s start-up, the thermostat is deactivated based on parameter timer tAF. By
adjusting GAL = 0, alarm reset is manual.
15
t31
ALARM Sensor No 3 - Sen3 (dFrost) – in Safety Thermostat mode. See parameter No 34
t3E
16
t32
ALARM Sensor No 5 – Sen5 (dFrost) – in Safety Thermostat mode. See parameter No 34
t3E
17
nH1
HP1 transmitter failure. HIGH PRESSURE circuit 1
18
nH2
HP2 transmitter failure. HIGH PRESSURE circuit 2
19
P1H
ALARM
HP1
from the transmitter 4-20 mA of the 1st circuit. OFF the compressors. RESET manual optional.
20
P2H
ALARM
HP2
from the transmitter 4-20 mA of the 1st circuit. OFF the compressors. RESET manual optional.
21
Pr1
ALARM
PREVENT
4-20 mA high pressure sensor of the 1st circuit. When the circuit pressure becomes greater than the value of the
PrE
parameter the
ALARM PREVENT (
Pr1
) is activated and OFFs the second compressor or CAPACITIEVE of the 1st circuit
22
Pr2
ALARM
PREVENT
4-20 mA high pressure sensor of the 2
nd
circuit. When the circuit pressure becomes greater than the value of the
PrE
parameter the
ALARM PREVENT (
Pr2
) is activated and OFFs the second compressor or CAPACITIEVE of the 2
nd
circuit
The alarms are automatically deactivated when the cause of the alarm disappears.