KIOUR MACON HP Скачать руководство пользователя страница 5

No

 

PARAMETERS

 

DESCRIPTION

 

min

 

max

 

DEFAULT

 

UoM

 

105 

C2d 

C2.  Lower  analog  output  voltage.  Compressor  C2  of  the  2

nd

  circuit.  The  analog  signal  0-10  Volt 

corresponds consistently to C2. Values from 0 to 4.0 Volts. The analog output will be between 

C2U -

 

C2d

 in a temperature range defined by the parameter 

C2H

 or 

C2C

. For example, 

C2U - C2d = 7

 and 

C2H = 3

 and 

SHt =45°C

, the voltage will change 

10-3Volt

 from 

42 ÷ 45°C

 on heating (see

 

figure 5B). 

3,0 

Volt 

106 

C2U 

C2. Higher voltage at the analog output.

 

10 

10,0 

Volt 

107 

C2H 

C2. In the heating. Temperature / pressure range to which the analog output voltage corresponds.

 

1.0 

25.0 

3.0 

°C 

108 

C2C 

C2. In the cooling. Temperature / pressure range to which the analog output voltage corresponds. 

1.0

 

25.0

 

3.0

 

°C

 

109 

C2i

 

C2. Reverse analog signal at the output

 

units 

110 

C2A 

C2. Increasing the value reduces the oscillation of the 0-10 Volt signal. 

1

 

40

 

5

 

units

 

111 

F2d 

FAN 2. Lower analog output voltage. 2nd circuit. Values from 0 to 4.0 Volt. The analog output will 
range between 

F2U - F2d

 in a temperature range defined by parameter 

F2H

 or 

F2C

. For example, 

F2U - F1d = 7

 and 

F2H = 3

 and 

SHt = 45 °C

, the voltage will change 

10-3 Volt

 from 

42 ÷ 45 °C

 on 

heating  (see  figure  6B).  When  the  relays 

C2

C2b

  are  OFF  then  the  analog  output  is  zero. 

 In the DRIPING_TIME phase it produces the maximum voltage. 

3,0 

Volt 

112 

F2U 

FAN 2. Higher voltage at the analog output.  
When the relay of FAN 2 is OFF then the analog output is 0 Volt 

10 

10,0 

Volt 

113 

F2H

 

FAN 2. In the heating. 
Temperature / pressure range to which the analog output voltage corresponds.

 

1.0 

25.0 

3.0

 

°C 

114 

F2C 

FAN 2. In the cooling. 
Temperature / pressure range to which the analog output voltage corresponds.

 

1.0 

25.0 

3,0 

°C 

115 

F2i

 

FAN2. Reverse analog signal at the output

 

units 

116 

F2A 

FAN 2. Increasing the value reduces the oscillation of the 0-10 Volt signal 

1

 

40

 

5

 

units

 

117 

VtO 

In case the machine is OFF. Time OFF of the valves after the minutes specified by the parameter 
(See 

EOV

 parameter). 

20 

min 

118 

EOV 

If 

EOV = 0

 and the system is OFF, then the valves are OFF after the time specified by parameter 

VtO

If 

EOV = 1

 the valves remain in the state specified by the 

GSu

 parameter. 

units 

119 

PrE 

PREVENT

. In case the pressure of circuit 1 becomes higher than the value of the parameter, the 

ALARM PREVENT 

(Pr1)

 is activated and turns OFF the 2

nd

 compressor or CAPACITIVE of the 1st 

circuit. The same applies to the second circuit. (

Pr2

). Activated if 

PEn = 1

 and with the parameters 

SH1 = 1

 and 

SH2 = 1

 respectively for circuit 1 and 2. With 

itY = 3

 (1 compressor / circuit) PREVENT 

is deactivated. 

PrE

 Set Point works without differential.

 

5,0 

99,9 

40,0 

units 

120 

HPA 

In case the pressure of circuit 1 becomes higher than the value of the parameter, the high pressure 
ALARM is activated by the transmitter (

P1H

), and turns OFF the compressors of the 1st circuit. The 

same applies to the second circuit, called ALARM 

P2H

. Activated if HEn = 1 and with the parameters 

SH1 = 1

 and 

SH2 = 1

 respectively for circuit 1 and 2.  

The SET POINT of 

HPA

 works without differential. 

5,0 

99,9 

40,0 

units 

121 

PEn 

Value

=0

 Deactivate the parameter 

PrE. 

Value 

=1

 activate the 

PrE 

parameter. 

units 

122 

HEn

 

Value

=0

 Deactivate the parameter 

HPA. 

Value 

=1

 activate the 

HPA 

parameter. 

units 

123 

CAV 

Reverse operation of CAPACITIVE, C1b and C2b relays. Value 

= 0

 => ON the relay on the thermostat 

ON. Value 

= 1

 => OFF the relay on the thermostat ON. 

units 

124 

LPA 

ALARM Operation of Low Pressure when the compressor is OFF. 
Value

=0

 => Blocks ALARM. Value 

= 1

  => ALARM is free

 

units 

 

ALARM TABLE 

 

Display flashes when the alarm messages are displayed

 

HP1 

ALARM HIGH PRESSURE C1: Stops the operation of compressor C1. By adjusting parameter GAL = 0, alarm reset is manual. 

LP1 

ALARM LOW PRESSURE C1: Stops the operation of compressor C1. By adjusting parameter GAL = 0, alarm reset is manual. 

C1 

ALARM COMPRESSOR C1: Stops the operation of compressor C1. Alarm is only automatically deactivated when the cause of the alarm disappears. 

FLS 

ALARM FLOW SWITCH: ALARM from the FLOW SWITCH. By adjusting parameter GAL = 0, alarm reset is manual. 

HP2 

ALARM HIGH PRESSURE C2: Stops the operation of compressor C2. By adjusting parameter GAL = 0, alarm reset is manual. 

LP2 

ALARM LOW PRESSURE C2: Stops the operation of compressor C2. By adjusting parameter GAL = 0, alarm reset is manual. 

C2 

ALARM COMPRESSOR C2: Stops the operation of compressor C2. Alarm is only automatically deactivated when the cause of the alarm disappears. 

Ar1 

ALARM SENSOR 1: ALARM analog input Νο 1. Safety thermostat. (Water input). Sensor malfunction. Alarm is only automatically deactivated when the cause 
of the alarm disappears. 

Ar2 

ALARM SENSOR 2: ALARM analog input Νο 2. Safety thermostat. (Water output). Circuit 1. Sensor malfunction. Alarm is only automatically deactivated 
when the cause of the alarm disappears.

 

10 

Ar3 

ALARM SENSOR 3: ALARM analog input Νο 3. Defrost Sensor malfunction. Alarm is only automatically deactivated when the cause of the alarm disappears.

 

11 

Ar4 

ALARM SENSOR 4: ALARM analog input Νο 4. Safety thermostat. (Water output). Circuit 2. Sensor malfunction. Alarm is only automatically deactivated 
when the cause of the alarm disappears. 

12 

Ar5 

ALARM SENSOR 5: ALARM analog input Νο 5. Defrost. Sensor malfunction. Alarm is only automatically deactivated when the cause of the alarm disappears.

 

13 

At1 

ALARM FROST: ALARM from the Safety Thermostat Circuit 1. At compressor’s start-up, the thermostat is deactivated based on parameter timer tAF. By 
adjusting GAL = 0, alarm reset is manual.

 

14 

At2 

ALARM FROST: ALARM from the Safety Thermostat Circuit 2. At compressor’s start-up, the thermostat is deactivated based on parameter timer tAF. By 
adjusting GAL = 0, alarm reset is manual.

 

15 

t31 

ALARM Sensor No 3 - Sen3 (dFrost) – in Safety Thermostat mode. See parameter No 34 

t3E

  

16 

t32 

ALARM Sensor No 5 – Sen5 (dFrost) – in Safety Thermostat mode. See parameter No 34 

t3E

  

17 

nH1 

HP1 transmitter failure. HIGH PRESSURE circuit 1

 

18 

nH2 

HP2 transmitter failure. HIGH PRESSURE circuit 2

 

19 

P1H 

ALARM 

HP1

 from the transmitter 4-20 mA of the 1st circuit. OFF the compressors. RESET manual optional.

 

20 

P2H 

ALARM 

HP2 

from the transmitter 4-20 mA of the 1st circuit. OFF the compressors. RESET manual optional.

 

21 

Pr1 

ALARM 

PREVENT

 4-20 mA high pressure sensor of the 1st circuit. When the circuit pressure becomes greater than the value of the 

PrE

 parameter the 

ALARM PREVENT (

Pr1

) is activated and OFFs the second compressor or CAPACITIEVE of the 1st circuit

 

22 

Pr2 

ALARM 

PREVENT

 4-20 mA high pressure sensor of the 2

nd

 circuit. When the circuit pressure becomes greater than the value of the 

PrE

 parameter the 

ALARM PREVENT (

Pr2

) is activated and OFFs the second compressor or CAPACITIEVE of the 2

nd

  circuit

 

The alarms are automatically deactivated when the cause of the alarm disappears.

 

 
 
 

Содержание MACON HP

Страница 1: ...an monitor all temperatures compressors relays alarms parameters while sending SMS and emails in case of an alarm More than 250 devices can connect to this network Connect to a Remote Control device it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device It can be installed up to 500 meters away from the main device PARAMETERS Para...

Страница 2: ...mpressor C2b operation hours hours A15 Hs1 out of order A16 Hs2 out of order 1 SCo SET POINT of compressor in Cooling mode LCL LCH 10 C 2 SHt SET POINT of compressor in Heating mode LHL LHH 20 C 3 Cod Access code with Cod 22 we access all the following parameters 0 255 0 4 diS Adjust which sensor is displayed on screen where 1 sensor 1 etc 1 5 1 5 rCo Differential of SET POINT in Cooling mode 0 1 ...

Страница 3: ...t Point rH1 Below Set Point resistance is ON 0 1 1 units 39 rC1 activation deactivation of the cooling resistance ON based on Set Point rSC Below Set Point resistance is ON 5 C 0 1 1 units 40 rSC Resistance Set Point Cooling Below Set Point resistance is ON 5 C Works with T2 T4 50 150 15 0 C 41 SE1 out of order 0 1 1 units 42 SE2 Sensor activation Νο 2 where 0 sensor deactivated 1 sensor activated...

Страница 4: ...circuits Values 1 One circuit 2 Two circuits 1 2 2 units 86 GLE out of order 0 255 0 87 GPo Compressor boot time in Power Up 0 200 0 sec 88 GLC Value 0 gives priority to the compressor with the fewest hours 1 gives constant priority to the compressor 1 2 gives constant priority to the compressor 2 0 2 0 units 89 GFP Pump operation with ALARM safety thermostat in OFF machine condition 0 the pump is...

Страница 5: ... and C2b relays Value 0 ON the relay on the thermostat ON Value 1 OFF the relay on the thermostat ON 0 1 0 units 124 LPA ALARM Operation of Low Pressure when the compressor is OFF Value 0 Blocks ALARM Value 1 ALARM is free 0 1 1 units ALARM TABLE Display flashes when the alarm messages are displayed 1 HP1 ALARM HIGH PRESSURE C1 Stops the operation of compressor C1 By adjusting parameter GAL 0 alar...

Страница 6: ...P2 Drainage procedure of the 2nd circuit after deFrost 3 dF1 dFrost is running on the 1st circuit 4 dF2 dFrost is running on the 2nd circuit On the MACON_HPB the flashing LED in position No 2 indicates that the device is communicating with the main unit The LED in position of terminal No 11 indicates that the device is under voltage The same applies to compressor C2 respectively with parameters C2...

Страница 7: ...The same applies to FAN 2 respectively with the parameters F2d F2U F2C ...

Страница 8: ... sensor No 1 Water inlet circuit 1 Thermostat operation HEATING COOLING Temperature sensor No 2 Water outlet Safety thermostat No 1 Resistance No 1 Temperature sensor No 3 deFrost control Temperature sensor No 4 Water outlet circuit 2 Safety thermostat No 2 Resistance No 2 Temperature sensor No 5 Defrost control C2 ...

Страница 9: ...g magnets in areas affected by direct sunlight or rain Prevent electrostatic discharges and sharp objects from been inserted to the device Separate signal cables from power supply cables to prevent electromagnetic disorders Signal cables must never be in the same pipe with the power supply cables The device is under two year s guarantee The guarantee is valid only if the manual instructions have b...

Отзывы: