No

 

PARAMETERS

 

DESCRIPTION 

min

 

max

 

DEFAULT

 

UoM

 

18 

dEn 

Temperature ending defrost 

With  the  parameter 

dto  =  1

  the  defrost  ends  when  it  reaches  this  temperature  in  less  than  the 

maximum duration of the defrost. With the parameter 

t3E = 1

 it functions as a differential 

(differential = 

dEn - dbE

) safety thermostat of the temperature 

SEn3

SE55

 

-50 

150 

15.6 

°C

 

19 

dFA 

Over this temperature, the 

fan

 is ON during defrost. Differential is 1 °C. 

-50 

150 

16.4 

°C

 

20 

dt1 

Time frame in which all defrost requirements must occur in order to start defrost

 

200 

min 

21 

dt2 

Minimum time defrost duration, 

where 1 unit = 10 sec 

200 

10sec 

22 

dt3 

Maximum time defrost duration

 

200 

min 

23 

dt4 

Minimum time between two successive defrosts of the same circuit

 

200 

min 

24 

dt5 

Minimum time between two successive defrost of the two circuits 

200 

min 

25 

dt6 

ON or OFF time of the valve at the start and end of dFrost.  
If this function is enabled by the 

dFS

 parameter. 

20 

min 

26 

dFS 

dFrost value, where: 

0 =

 At the start and at the end of deFrost the compressors stop

 

in order to rotate the valves with         

time 

dt6

  

1 =

 The valve rotates without stopping the compressor. 

units 

27 

d07 

Start of dFrost with 2 circuits. 
 

0 =

 Regardless 

 

1 =

 When both reach dFrost conditions 

 2 =

 When 1 of 2 reaches dFrost conditions 

units 

28 

d08 

0 =

. DFrost ends independently.  

1 =

 If one is finished, then the compressor turn OFF and waits for the other to finish. 

      In any case, both of them, end from the time pass. 

2 =

. If one ends, the other ends. 

units 

29 

drE 

State of resistance during dFrost.  

0 =

 OFF  ,  

1 =

 ON  

units 

30 

dF1 

FAN status in dFrost. 
 

0 =

 OFF , 

1 =

 works as in cooling with 

SP = FSC

 

units 

31 

dF2 

FAN. Evaporator drying after dFrost.  

0 =

 OFF , 

1-250 sec =

 FAN is ON with maximum drying speed. 

255 

sec 

32 

ASP 

SET POINT ALARM Antifreeze, Safety tthermostat 

 

 

 

-50 

60 

°C 

33 

Adi 

Differential , Safety Thermostat 

0,1 

20,0 

1.5 

°C 

34 

t3E 

0 =

 this function is disabled.  

1 =

. (for water coolers) activates the temperature 

SEn3

 and 

SEn5

 as a safety thermostat.  

DFrost is not needed and we turn it off. 

(doP = 0)

 

units 

35 

rSH 

Resistance SET POINT Heating. Below Set Point, resistance is ON. (Works with T2 , T4). 

-50 

60 

3.6 

°C 

36 

Adr 

Differential resistance thermostat. 

0,1 

20,0 

1,0 

°C 

37 

rOF 

Value 

=0

 => resistances OFF with whole system OFF. - frost conditions - . 

units 

38 

rH1 

activation / deactivation of the heating resistance. ON based on Set Point 

rH1

.

 

  

Below Set Point, resistance is ON. 

units 

39 

rC1 

activation / deactivation of the cooling resistance. ON based on Set Point 

rSC

.

 

  

Below Set Point, resistance is ON  (5°C). 

units 

40 

rSC 

Resistance Set Point Cooling. Below Set Point, resistance is ON (5°C). (Works with T2 , T4). 

-50 

+150 

15,0 

°C 

41 

SE1 

out of order 

units 

42 

SE2 

Sensor activation Νο 2, where 0 = sensor deactivated,  1 = sensor activated 

units 

43 

SE3 

Sensor activation Νο 3, where 0 = sensor deactivated,  1 = sensor activated 

units 

44 

SE4 

Sensor activation Νο 4, where 0 = sensor deactivated,  1 = sensor activated 

units 

45 

SE5 

Sensor activation Νο 5, where 0 = sensor deactivated,  1 = sensor activated 

units 

46 

SH1 

Value 

= 0

 => disables the input. Value 

= 1

 => Activates the 4-20 mA input of the high pressure of the 

1st circuit. (Transmitter HP1) (when there is transmitter failure the analog voltage of the FAN is at the 
maximum value). When transmitter is activated, the Set Point of the 

FSC

 and 

FSI

 parameters and the 

0-10 Volt output work based on the transmitter signal. DeFrost operation is run by temperature only. 

units 

47 

SH2 

Value 

= 0

 => disables the input. Value 

= 1

 => Activates the 4-20 mA input of the high pressure of the 

2

nd

 circuit. (Transmitter HP2) (when there is transmitter failure the analog voltage of the FAN is at the 

maximum value). When transmitter is activated, the Set Point of the 

FSC

 and 

FSH

 parameters and 

the 0-10 Volt output work based on the transmitter signal.  
DeFrost operation is run by temperature only.

 

units 

48 

SL1 

out of order

 

units 

49 

SL2 

out of order

 

units 

50 

rH1 

Adjustment  of  the  mA  scale.  1

st

  circuit  high  pressure  inlet  (HP1).  Display  the  correct  transmitter 

pressure range, for example instead of 0 – 100 units show 0 - 30,0 Bar.

 

10 

99,9 

100 

51 

rH2 

Adjustment  of  the  mA  scale.  2

nd

  circuit  high  pressure  inlet  (HP2).  Display  the  correct  transmitter 

pressure range, for example instead of 0 – 100 units show 0 - 30,0 Bar.

 

10 

99,9 

100 

52 

rL1 

Adjustment  of  the  mA  scale.  1

st

  circuit  low  pressure  inlet  (LP1).  Display  the  correct  transmitter 

pressure range, for example instead of 0 – 100 units show 0 - 30,0 Bar.

 

10 

99,9 

100 

53 

rL2 

Adjustment  of  the  mA  scale.  2

nd

  circuit  low  pressure  inlet  (LP2).  Display  the  correct  transmitter 

pressure range, for example instead of 0 – 100units show 0 - 30,0 Bar.

 

10 

99,9 

100 

54 

AJ1 

Sensor No 1 offset 

-9,0 

15,0 

°C 

55 

AJ2 

Sensor No  2 offset 

-9,0 

15,0 

°C 

 

AJ3 

Sensor No  3 offset 

-9,0 

15,0 

°C 

56 

AJ4 

Sensor No 4 offset 

-9,0 

15,0 

°C 

57 

AJ5 

Sensor No 5 offset 

-9,0 

15,0 

°C 

58 

AJ6 

out of order

 

-

 

-

 

-

 

-

 

59 

AJ7 

out of order

 

-

 

-

 

-

 

-

 

60 

AJ8 

out of order

 

-

 

-

 

-

 

-

 

61 

AJ9 

out of order

 

-

 

-

 

-

 

-

 

Содержание MACON HP

Страница 1: ...an monitor all temperatures compressors relays alarms parameters while sending SMS and emails in case of an alarm More than 250 devices can connect to this network Connect to a Remote Control device it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device It can be installed up to 500 meters away from the main device PARAMETERS Para...

Страница 2: ...mpressor C2b operation hours hours A15 Hs1 out of order A16 Hs2 out of order 1 SCo SET POINT of compressor in Cooling mode LCL LCH 10 C 2 SHt SET POINT of compressor in Heating mode LHL LHH 20 C 3 Cod Access code with Cod 22 we access all the following parameters 0 255 0 4 diS Adjust which sensor is displayed on screen where 1 sensor 1 etc 1 5 1 5 rCo Differential of SET POINT in Cooling mode 0 1 ...

Страница 3: ...t Point rH1 Below Set Point resistance is ON 0 1 1 units 39 rC1 activation deactivation of the cooling resistance ON based on Set Point rSC Below Set Point resistance is ON 5 C 0 1 1 units 40 rSC Resistance Set Point Cooling Below Set Point resistance is ON 5 C Works with T2 T4 50 150 15 0 C 41 SE1 out of order 0 1 1 units 42 SE2 Sensor activation Νο 2 where 0 sensor deactivated 1 sensor activated...

Страница 4: ...circuits Values 1 One circuit 2 Two circuits 1 2 2 units 86 GLE out of order 0 255 0 87 GPo Compressor boot time in Power Up 0 200 0 sec 88 GLC Value 0 gives priority to the compressor with the fewest hours 1 gives constant priority to the compressor 1 2 gives constant priority to the compressor 2 0 2 0 units 89 GFP Pump operation with ALARM safety thermostat in OFF machine condition 0 the pump is...

Страница 5: ... and C2b relays Value 0 ON the relay on the thermostat ON Value 1 OFF the relay on the thermostat ON 0 1 0 units 124 LPA ALARM Operation of Low Pressure when the compressor is OFF Value 0 Blocks ALARM Value 1 ALARM is free 0 1 1 units ALARM TABLE Display flashes when the alarm messages are displayed 1 HP1 ALARM HIGH PRESSURE C1 Stops the operation of compressor C1 By adjusting parameter GAL 0 alar...

Страница 6: ...P2 Drainage procedure of the 2nd circuit after deFrost 3 dF1 dFrost is running on the 1st circuit 4 dF2 dFrost is running on the 2nd circuit On the MACON_HPB the flashing LED in position No 2 indicates that the device is communicating with the main unit The LED in position of terminal No 11 indicates that the device is under voltage The same applies to compressor C2 respectively with parameters C2...

Страница 7: ...The same applies to FAN 2 respectively with the parameters F2d F2U F2C ...

Страница 8: ... sensor No 1 Water inlet circuit 1 Thermostat operation HEATING COOLING Temperature sensor No 2 Water outlet Safety thermostat No 1 Resistance No 1 Temperature sensor No 3 deFrost control Temperature sensor No 4 Water outlet circuit 2 Safety thermostat No 2 Resistance No 2 Temperature sensor No 5 Defrost control C2 ...

Страница 9: ...g magnets in areas affected by direct sunlight or rain Prevent electrostatic discharges and sharp objects from been inserted to the device Separate signal cables from power supply cables to prevent electromagnetic disorders Signal cables must never be in the same pipe with the power supply cables The device is under two year s guarantee The guarantee is valid only if the manual instructions have b...

Отзывы: