Control device CHILLER / heat pump for 1 or 2 circuits with 2 or 4 compressors,                                                                

 

with analog outputs 0-10 Volt in compressors and fans.  

Models: MACON_HP (panel), MACON_HPR (rail) (1

st

  circuit) and MACON_HPB (rail), (2

nd

  circuit)

 

V.2.1    

DESCRIPTION

 

MACON_HP

 controller is suitable for controlling a chiller or 2-circuit heat pump. Available in 28x70mm box or in 70mm rail box. The second circuit (

MACON_HPB

) is 

available in a 70mm rail box and is connected to the main unit via three cables.

  

MACON_HP (1st circuit) has the following specifications

MACON_HPB (2

nd  

circuit) has the following specifications

 

3 analog inputs

 for measuring temperature with 

range -50 ÷ +150°C     

1 analog high pressure input (HP1) 4-20 mA for transmitter 

 

 

2 analog inputs

 for measuring temperature with 

range -50 ÷ +150°C 

1 analog high pressure input (HP1) 4-20 mA for transmitter 

 

SENsor 1. Water input circuit 1. Operation thermostat HEATING - COOLING 

SENsor 4. Water output 2

nd

 circuit. Safety thermostat Νo2. Resistance Νo2 

SENsor 2. Water output. Safety thermostat Νo1. Resistance Νo1 
 

 

SENsor 5. Defrost C2 control (2

nd

 circuit.) 

SENsor 3. Defrost control C1 (Compressor 1

st

 ) 

 
 

 

 

6 digital inputs

:   

 

3 digital outputs

1st  input    

 Terminal block 15. ΟΝ-OFF device from a remote switch 

 

 

 

7

th

    input   

 Terminal block 23  HΡ2.   High pressure 2

nd

  circuit 

2

nd

  input    

 Terminal block 16  HEAT-COOL from a remote switch 

 

8

th

    input   

 Terminal block 22  LP2.    Low pressure 2

nd

  circuit 

3

rd

   input   

 Terminal block 17  HP1.  High pressure 1

st

 circuit 

 

9

th

    input   

 Terminal block 21  C2.      Thermal of 2

nd

  circuit compressor 

4

th

   input   

 Terminal block 18  LP1.  Low pressure 1

st

  circuit 

 

 

5

th

   input   

 Terminal block 19  C1.  Thermal of 1

st

 circuit compressor 

 

 

6

th

   input   

 Terminal block 20  FLOW SWITCH.  

 

 

 

7  relay  outputs 

250VAC  5Amp:  pump  relay,  compressor 

C1

,  valve 

V1

resistance 

R1

, fan 

FAN 1

, alarm, compressor 

C1b

 Tadem or capacitive. 

 

2 analog output 0-10 Volt 

 

 Compressor C1 

(Terminal blocks 25, 28), and 

for the fan 

FAN1

 (Terminal blocks 25, 27).

 

 

5 relay outputs

 250VAC 5Amp: compressor

 

relay

 C2,

 valve 

V2, 

resistance 

R2,

 fan

 

FAN 2, 

compressor 

C2b

 Tadem or capacitive

 
2 analog output 0-10 Volt 

 

 Compressor C2 

(Terminal blocks 7, 8) and for the 

fan 

FAN2

 (Terminal blocks 6, 8). 

 

 

 

CONNECT TO NETWORK 

The device can connect to a PC via network RS485 or to a Remote Control via four cables. 

 

Connect to a PC: CAMIN software can monitor all temperatures, compressors relays, alarms, parameters, while sending SMS and emails in case of an alarm. 
More than 250 devices can connect to this network.   

 

Connect to a Remote Control device: it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device. 
It can be installed up to 500 meters away from the main device.

 

PARAMETERS 

Parameters are separated in two groups: 120 main parameters and 16 secondary parameters (A1-A16). Two of the main and 16 of the secondary parameters are easy 
accessible. For the rest we have to enter in the parameter Cod = 22 to have access to all the parameters

.

 Check relevant table on page 2. 

TECHNICAL SPECIFICATIONS 

Power supply: 24 VAC/DC 50/60 Hz 10W   
Connection with terminal blocks 28-16 AWG 1.5 mm

2

 

7 relays 250VAC 5A/3A Resistive Load in MACON_HP

 

5 relays 250VAC 5A Resistive Load in MACON_HPΒ

 

Operation temperature:  -10 

÷

 +50 °C

 

Storage temperature: -20 

÷

 +80 °C 

MACON_HP is mounted on a panel / Dimensions 28x70x75mm 
MACON_HPΒ is mounted on a Ω rail / Dimensions 70x90x65mm 
It is suggested using a safety switch 1Α (not included)  
Maximum consumption for each device 10 Watt 

 ON/OFF DEVICE 

Press 

 for 4 seconds to toggle the device between 

ON/OFF

 

state if the parameter is set to

 Grc=0

.  

If ON-OFF input No 15 is activated or if the parameters are under programming, this function is canceled. 

 HEATING – COOLING OPERATION 

Press 

 for 4 seconds  to toggle the operation between heating and cooling or cooling and heating mode if parameter is set to 

GrH=0. 

If the input No 16 Heating-Cooling is activated or the parameters are under programming, this operation is cancelled. 

dFrost 

Pressing the SET button for 5 sec starts dFrost on both circuits. The display shows the message dF1 and dF2 every 2 sec, for a fraction of a second, which means that 
circuits 1 and 2 do dFrost. 
 

RESET ALARMS 

Pressing 

 to reset the alarms: this feature is active even during programming the parameters. 

 

PROGRAMMING PARAMETERS 

Press 

  to 

enter

 or 

exit

 the parameters menu. 

The first parameter “

SCo”

 is displayed and with the 

,

 we scroll into the parameters menu. 

Press 

SET

 to 

display

 the parameters value and adjust it with the 

,

Press 

  to 

confirm

 the new value and display the parameters name. 

Press 

SET

 to 

cancel

 the new value and revert to the parameters name.  

NOTE

: for safety reasons all parameters as presented to the parameters table are not displayed. We must enter parameter Cod=22 to access full parameters menu. 

 
 

Содержание MACON HP

Страница 1: ...an monitor all temperatures compressors relays alarms parameters while sending SMS and emails in case of an alarm More than 250 devices can connect to this network Connect to a Remote Control device it displays on screen whatever is displayed on the main device and it has full access from the keyboard to the main device It can be installed up to 500 meters away from the main device PARAMETERS Para...

Страница 2: ...mpressor C2b operation hours hours A15 Hs1 out of order A16 Hs2 out of order 1 SCo SET POINT of compressor in Cooling mode LCL LCH 10 C 2 SHt SET POINT of compressor in Heating mode LHL LHH 20 C 3 Cod Access code with Cod 22 we access all the following parameters 0 255 0 4 diS Adjust which sensor is displayed on screen where 1 sensor 1 etc 1 5 1 5 rCo Differential of SET POINT in Cooling mode 0 1 ...

Страница 3: ...t Point rH1 Below Set Point resistance is ON 0 1 1 units 39 rC1 activation deactivation of the cooling resistance ON based on Set Point rSC Below Set Point resistance is ON 5 C 0 1 1 units 40 rSC Resistance Set Point Cooling Below Set Point resistance is ON 5 C Works with T2 T4 50 150 15 0 C 41 SE1 out of order 0 1 1 units 42 SE2 Sensor activation Νο 2 where 0 sensor deactivated 1 sensor activated...

Страница 4: ...circuits Values 1 One circuit 2 Two circuits 1 2 2 units 86 GLE out of order 0 255 0 87 GPo Compressor boot time in Power Up 0 200 0 sec 88 GLC Value 0 gives priority to the compressor with the fewest hours 1 gives constant priority to the compressor 1 2 gives constant priority to the compressor 2 0 2 0 units 89 GFP Pump operation with ALARM safety thermostat in OFF machine condition 0 the pump is...

Страница 5: ... and C2b relays Value 0 ON the relay on the thermostat ON Value 1 OFF the relay on the thermostat ON 0 1 0 units 124 LPA ALARM Operation of Low Pressure when the compressor is OFF Value 0 Blocks ALARM Value 1 ALARM is free 0 1 1 units ALARM TABLE Display flashes when the alarm messages are displayed 1 HP1 ALARM HIGH PRESSURE C1 Stops the operation of compressor C1 By adjusting parameter GAL 0 alar...

Страница 6: ...P2 Drainage procedure of the 2nd circuit after deFrost 3 dF1 dFrost is running on the 1st circuit 4 dF2 dFrost is running on the 2nd circuit On the MACON_HPB the flashing LED in position No 2 indicates that the device is communicating with the main unit The LED in position of terminal No 11 indicates that the device is under voltage The same applies to compressor C2 respectively with parameters C2...

Страница 7: ...The same applies to FAN 2 respectively with the parameters F2d F2U F2C ...

Страница 8: ... sensor No 1 Water inlet circuit 1 Thermostat operation HEATING COOLING Temperature sensor No 2 Water outlet Safety thermostat No 1 Resistance No 1 Temperature sensor No 3 deFrost control Temperature sensor No 4 Water outlet circuit 2 Safety thermostat No 2 Resistance No 2 Temperature sensor No 5 Defrost control C2 ...

Страница 9: ...g magnets in areas affected by direct sunlight or rain Prevent electrostatic discharges and sharp objects from been inserted to the device Separate signal cables from power supply cables to prevent electromagnetic disorders Signal cables must never be in the same pipe with the power supply cables The device is under two year s guarantee The guarantee is valid only if the manual instructions have b...