Varisol Installation Manual
Key
1 Drain connection
2 Fill connection
3 Flow meter
4 Isolating valve
5 Motorised pump
6 6 bar pressure relief valve
7 Expansion vessel connection
8 Pressure guage
9 22mm connections
10 Temperature guage
11 Air separator
12 Insulated fascia
13 Pressure relief discharge point
The Kingspan Solar product range offers both a single stream and a dual stream
pump station. Each pump station is available in various sizes to suit the required flow
rate of the system.
The flow rate required on a system is typically 1 litre per minute, per square metre
installed for systems up to 12m
2
. Therefore a 2-12 litre/minute pump station should
be sufficient for systems up to 12m
2
.
Connections of flow and return pipe work to the pump station are made with the
straight compression fittings provided for direct copper connection.