Venting Routes And Components

Since it is very important that the vent system maintain its balance
between the combustion air intake and the flue gas exhaust, certain lim-
itations as to vent configurations apply and must be strictly adhered to.

The table showing the relationship between vertical and horizontal side
wall venting will help to determine the various vent lengths.

The maximum horizontal run with the 90 degree bend at the fireplace
flue outlet is 4 ft/122cm (Figure #1). The maximum horizontal run is
20 ft/6.1 m when the vertical run is 7 ft/2.1m (Figure #2). Note: 1/4”
vertical rise is required for every 12” of horizontal run.

The maximum number of 45 degree bends per side wall installation is
two (2) in the horizontal run and then you must reduce the length of the
horizontal by 18 inches for each 45 degree bend.

The maximum vertical run is 40 ft/12.2 meters.

Special Note: For each 45 degree bend installed in the horizontal
run, the length of the horizontal run must be reduced by 18”
(45cm). This does not apply if the 45 degree bends are installed on
the vertical part of the vent system.

Example: 

If according to the table, the length of the horizontal run is

10 feet, and two 45 degree bends are required, the horizontal run length
must be reduced to 7 feet.

2 additional 90° bends or equals are allowed.  The horizontal run must
be reduced by 36” per each 90° bend, or 18” per each 45° bend.

How To Use The Horizontal Vent Table

1. Determine the height of the system and the number of bends

required.

2. Having determined the vertical distance determine the maximum

horizontal section allowed.

3. Vent table has been established for 90˚ horizontal/vertical runs.

With use of flex pipe distance not having 90˚ bends will not fall into
vent table standards. See Fig. B.

Horizontal Venting Table From Bottom of Fireplace

for venting to a maximum of 40 ft. (12.2 meters)

Total Vertical

Max Total Horizontal

Feet

Meters

Feet Meters

4

1.2

5

1.5

5

1.5

8

1.2

6

1.8

12

3.7

7

2.1

20

6.1

8

2.4

20

6.1

9

2.7

20

6.1

10

3.0

20

6.1

11

3.4

20

6.1

12

3.7

20

6.1

13

4.0

20

6.1

14

4.3

20

6.1

15

4.6

20

6.1

16

4.9

20

6.1

17

5.2

20

6.1

18

5.5

20

6.1

19

5.8

20

6.1

20

6.1

20

6.1

25

7.5

15

4.6

30

9

10

3.0

40

12.2

0

0

Example A:

If the vertical dimension from
the floor of the fireplace is 6ft,
the horizontal run to the wall
flange of the vent termination
must not exceed 12ft.

NOTE: The final location of
the fireplace must be such
that the horizontal vent
dimensions fall within those
stated on the graph. The
Maximum Vertical vent run
is 40ft. (12.2 meters).

Important: 

Always locate the fireplace in such a way that a minimum of off-

sets and/or horizontal runs are required. 1/4” vertical rise is required for every
12”  horizontal run.

Important: 

Minimum clear-

ance between vent pipes and
combustible materials is 1 inch
(25mm).

12 ft.

6 ft.

34"

MINIMUM

SUPPORT STRAP ON 

90° BEND

MAX. HORIZONTAL

FIGURE A

FIGURE B

TOT

AL VER

TICAL

It is recommended for 

Propane Horizontal Installations

that the

venting should be a minimum of one foot vertical off the flue
before the elbow on any horizontal runs of one foot or greater.
This allows for cleaner combustion and greatly reduces carboning
and cleaning of glass.  (Does not apply to Back Flue Models).

20 FEET

Содержание ZDV3624

Страница 1: ...with other gases unless a certified kit is used Read this complete manual before beginning installation These instructions must be kept with the unit for future reference FOR YOUR SAFETY Warning Impro...

Страница 2: ...tory However due to the high temperature sili cone components the paint will cure when heat is applied to the appliance as it is first used The following information applies to the curing process to g...

Страница 3: ...22 Millivolt system lighting burner control 23 Vent termination 24 Venting graph 25 General vent installation information 26 Installation of side wall venting 26 Venting vertical 27 Back Vent 30 Repa...

Страница 4: ...al Electrical Code in Canada An appliance must be grounded to the steel chassis of the home with 8 ga copper wire using a serrated or star washer to penetrate paint or protective coating to insure gro...

Страница 5: ...be used in this appliance 10 For safe operation glass doors must be closed 11 Do not use this heater if any part has been under water Immediately call a qualified service technician to inspect the he...

Страница 6: ...xceed 20 feet 6 1 m When you install your fireplace as in position B D or E a minimum of 6 inches 153mm clearance must be maintained from the perpendicular wall and the front of the appliance A Flat o...

Страница 7: ...enclosures 5 Hearth is not mandatory but is recommended for aesthetic purposes Combustible floors cannot raise above the bottom of the fireplace We recommend a non combustible hearth projecting out 12...

Страница 8: ...quer must be heat resistant 250 F to prevent discoloration Warning Combustible objects must not be placed on a non combustible mantel unless the non combustible mantel meets the minimum height and wid...

Страница 9: ...supply piping system at test pres sures equal to or less than 1 2 PSIG 3 5 KPa Note The gas line connection may be made of 1 2 rigid pipe 1 2 copper pipe or an approved flex connector Since some muni...

Страница 10: ...s will void all product warranties Care must be taken to avoid breakage of the glass Do not operate this fireplace without the glass front or with a broken glass front Do not strike or abuse glass Gla...

Страница 11: ...k burner Step 4 Break glowing embers into thumbnail size Place glowing embers on to the surface of the front burner to the surface of the ember plates and over crossover to the same height as ember pl...

Страница 12: ...ce right crossover log across front and back logs using the log placement pin as a guide Step 8 Place left crossover log across front and back logs using the log placement pin as a guide Step 9 Place...

Страница 13: ...URE B Rear log holder If using LOGC44 bend rear tabs 90 down Step 1 Position rear log over rear log holder and lower into position Be sure that the log does not sit on rear burner but behind and lower...

Страница 14: ...tear off dime and nickel sized pieces and place directly onto front burner tube and crossover tube NOTE Do not place embers onto rear burner tube Step 5 Position Log 4 into grooved areas of Logs 1 an...

Страница 15: ...ween Log 1 and Log 2 Step 9 Position Log 8 up against the 3rd grate post from the right and position upper section of Log 8 against Logs 2 and 7 Step 10 Place crushed rocks onto firebox bottom NOTE Do...

Страница 16: ...rear burner log mount and push back against tab STEP 5 Place Log 5 against grate bars and position Log 6 along side of Log 5 and onto Log 1 as shown in the photograph STEP 6 Place the narrow end of L...

Страница 17: ...setting fully clockwise Use the set screw on the side of the variable speed controller to increase or decrease the minimum fan speed It may be desirable to lower minimum fan speed to decrease the sou...

Страница 18: ...odels are supplied with a wall switch that turns the main burner on or off If main burner does not light immediately when you turn the gas control valve to ON ensure that the wall switch is in the ON...

Страница 19: ...OOR FROM THE UNIT BY UNLATCHING THE 2 LATCH ES ON TOP OF THE UNIT 2 REMOVE THE FALSE BOTTOM FROM THE UNIT BY LIFTING STRAIGHT UP IT MAY NEED TO BE WIGGLED 3 PLACE REAR BRICK PANEL UP AGAINST THE REAR...

Страница 20: ...rizontal 11 2 Top of 90 degree elbow in an enclosure under 42 is 51 2 Top of 90 degree elbow in an enclosure over 42 is 21 2 Vent Terminal Air Supply Area Where Terminal Not Permitted A Clearance abov...

Страница 21: ...Having determined the vertical distance determine the maximum horizontal section allowed 3 Vent table has been established for 90 horizontal vertical runs With use of flex pipe distance not having 90...

Страница 22: ...le or an 8 diameter hole in a non combustible wall See Figure 2 2 Note clearance to combustible above 90 degree bend is 2 1 2 3 Select the approximate vent length precise measurements are not needed a...

Страница 23: ...Attic Insulation Shield where the chimney passes from a living space to an attic space install the shield from below and nail in place using 1 spiral nails 3 A fire stop must be installed on the bott...

Страница 24: ...e Retighten screw Reinstall burner at this time reversing STEPS 3 2 and 1 Step 11 Follow instructions supplied with the conver sion HI LOW to convert the valve from one type of fuel to the other Step...

Страница 25: ...of the injector 2 and rotate it counter clockwise until it is free of the injector journal 3 5 Verify that the new injector is proper for the application The injector size is stamped on the side of th...

Страница 26: ...RIABLE SPEED KBWC 13BV 1000 306 THERMALCORD ADHESIVE BACK FOR DOOR FRAME 1000 305 CERAMIC GLASS FOR ALL ZDV3600 3600 311 TEMPERED GLASS FOR ZDV3624 MODEL Step 3 Straight Back Venting Measure wall thic...

Страница 27: ...DV Fireplaces Conversion Kit Sit Valve Only 3624 CKLP LP Conversion Kit for ZDV3624 3624 CKNG NG Conversion Kit for ZDV3624 3628 CKLP LP Conversion Kit for ZDV3628 3628 CKNG NG Conversion Kit for ZDV...

Страница 28: ...m Pilot flame may be too low or Clean and or adjust pilot flame for maximum flame impingement blowing high causing the pilot on generator and thermocouple safety to drop out Flame lifts off burner and...

Страница 29: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: