ZCVRB47 -Framing Dimensions –Vented Chase -Ventilation Plates Removed
Determine whether face of fireplace will be:
Flush with finished wall (e.g., for surround, cultured stone or other non combustible covering).
Flush with framing (to be covered with concrete board for a Flat Wall appearance).
Refer to Nailing Tab Guide section also.
52” MIN
Plus Rise
of 1/4”
Per Foot
34-5/8”
To Face
Framing
Framing for Vent Termination
(See
Venting
Section)
Vertical Venting MUST maintain 1” clearance
to combustibles.
These structures are not load bearing.
Note: If using optional surround, maximum
thickness for non-combustible material is 3/4”.
Vertical Studs
notched for Grill
TV
Optional
Recess
70”
Minimum
Enclosure
70”
Minimum
Enclosure
Enclosure Top to Grill Opening
Ceiling
1”
Clearance
from Grill
Optional
Recess
TV
Ceiling
70”
Minimum
Enclosure
OPTIONAL RECESS
RECESSED TO CEILING
NO RECESS
70”
Minimum
Enclosure
52”
MIN
52”
MIN
Sealed Enclosure Top
Sealed Enclosure Top
Sealed Enclosure Top
HEAT CANNOT BE
DISCHARGED INTO THE
WALLS, FLOOR, OR
CEILING.
Heat must exit
through the required vented
chase opening near the
ceiling.
If using insulation in vented
chase (i.e. for outside wall),
wall board / drywall is
required to support all
insulation.
Vented chase must be clean
and free of all debris (i.e.
loose insulation, pieces of
wood, etc.).
MAX
MAX
70”
Minimum
Ceiling
Ceiling
TV
27