background image

12

INSTALLING

INSTALLATION OF
GLMVF38/GLMVF40 INTO 
EXISTING FIREPLACE

If installing in Canada or as a vented logset:

Appliance must be installed only in a solid fuel burning
fireplace with a working flue and constructed of non-
combustible material. See chart below for minimum per-
manent flue opening you must provide. The damper must
be secured so the minimum flue opening will be main-
tained at all times. This can be done by removing the
damper or welding the damper open.

Chimney Height

Minimum Permanent Flue

Opening
(feet)

(square inches)

6’ - 15’ 

39 square inches

15’ - 30’ 

29 square inches

Area of Various Standard Round Flues
Diameter (inside) Area (square inches)

5” 

20 square inches

6” 

29 square inches

7” 

39 square inches

8” 

51 square inches

The installation and the provisions for combustion and
ventilation air must conform with the National Fuel Gas
Code, ANSI Z223.1, or the CAN/CGA-B149, installation
codes

WARNING

Before installing in a solid fuel burning fireplace, the
chimney flue and firebox must be cleaned of soot, 
creosote, ashes, and loose paint by a qualified chimney
cleaner. Creosote may ignite when heated to a high
temperature. Have chimney flue inspected for damage. 

WARNING

Seal any fresh air vents or ash clean outdoors located
on the floor or wall of fireplace. If this is not done,
drafting may result causing pilot outage or sooting. Use
a heat-resistant sealant. Do not seal chimney flue
damper.

WARNING

This appliance is for installation in a solid-fuel burning
fireplace or approved ventless enclosure.

FIGURE 8  –  Installing GLMVF38/GLMVF40 into existing fireplace.

WARNING

Installation of vented gas logs in the Commonwealth of
Massachusetts requires the vent damper be permanently
removed or welded in the full open position. Vented gas
logs can not be installed in a bedroom or bathroom in
the Commonwealth of Massachusetts.

Содержание GLMVF38MVN

Страница 1: ...r the gas supplier Warning This is an unvented gas red heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventila tion air must be provided Refer t...

Страница 2: ...2...

Страница 3: ...ld leave the area during the cure phase Ventilate well open doors and windows Do not touch during curing Why does my replace or stove give off odour It is normal for your replace to give off some odou...

Страница 4: ...s 22 Illustrated Parts List for GLMVF38 23 24 Illustrated Parts List for GLMVF40 25 Troubleshooting 26 27 Warranty 28 GAS SPECIFICATIONS VENT FREE VENTED GAS LOG SETS Burner Log Set Fuel BTU Manifold...

Страница 5: ...ny other material on top of logs or logs into ame 5 Warning Always operate appliance with front re place screens closed and glass doors open 6 Make sure any safety screen or guard removed for ser vici...

Страница 6: ...Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition 22 Young children should be carefully supervised when they are...

Страница 7: ...erm 6 x 10 11 per pasec m2 or less with openings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints...

Страница 8: ...doors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used __________________ Btu Hr maximum the space can support __________________ Btu...

Страница 9: ...the wall connecting the two spaces see options 1 and 2 Figure 4 You can also remove door into adjoining room see option 3 Figure 4 Follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air...

Страница 10: ...12 of the ceiling and one within 12 of the oor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces IMPORTANT Do not provide openin...

Страница 11: ...perate the heater with the damper open MANTEL m FIGURE 6 Installation Clearances Minimum Fireplace Dimensions Front width Back Width Height Depth For GLMVF38 GLMVF40 34 34 19 1 2 19 1 2 MANTEL CLEARAN...

Страница 12: ...onform with the National Fuel Gas Code ANSI Z223 1 or the CAN CGA B149 installation codes WARNING Before installing in a solid fuel burning replace the chimney ue and rebox must be cleaned of soot cre...

Страница 13: ...caused Prepare incoming black iron gas line with Te on tape or pipe joint compound check with local codes about the use of Te on tape Compounds used on threaded joints of gas piping shall be resistant...

Страница 14: ...ce if a leak is detected CAUTION Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the heater NOTICE A quali ed gas appliance installer must connect the...

Страница 15: ...de to very dangerous lev els INSTALLING Log Grate ATTACHING LOG GRATE TO FIREPLACE BASE 1 Position log grate into replace and mark screw loca tions on each side of mounting bracket 2 Remove grate asse...

Страница 16: ...perimeter of the burner Do not place on middle burner as illustrat ed Care should be taken not to block burner ports Step 2 Take Log 4 and place onto burner using the two log tabs located on burner pa...

Страница 17: ...re Log 5 rests on the shape of Log 4 Log Pin Step 5 Place Log 3 onto both Log 1 and Log 5 using the log pins as a guide Log Pin Step 6 Place Log 2 onto both Log 1 and 4 using the log pins as a guide E...

Страница 18: ...ase of the replace and not blocking the 1 diameter hole in the bottom of the burner LOG31C A and B are packaged with the GLMVF40 Burner WARNING You must secure this heater to replace base or heater wi...

Страница 19: ...g hole on Log 3 Position hole on Tab 3 as shown Do not place log over the center burner tube 3 Locate the 2 mounting holes on the bottom of Log 4 and position them onto Tabs 4A and 4B Place V area of...

Страница 20: ...F40 BURNER GRATE 5 Place ember rocks on ember plates Warning Do not place ember rocks on the burner tubes 6 Place lava rock on the bottom of the re box surrounding the burner system Sprinkle vermiculi...

Страница 21: ...heater Use a soft bristle brush or a vacuum with brush attachment Vacuum loose particles and dust from burner ports valve and blower compartments Vacuum any accumulation of lint from primary mixing tu...

Страница 22: ...heat build up inside replace will cause glass to burst WARNING A replace screen must be in place when the appli ance is operating and unless other provisions for combustion air are provided the screen...

Страница 23: ...BRACKET 9 1 38GL 106 PILOT BRACKET 10 4 MISC HEX SCREW 11 4 MISC 500 X 200 WASHER 12 1 33VF P8214 ODS PILOT 13 1 33VF P637si NOVASIT 820 14 1 33VF P112ve 1 5 X 375 NIPPLE 15 1 1000 257 ELBO90 375 X 12...

Страница 24: ...38GL 105 BURNER BRACKET 9 1 38GL 106 PILOT BRACKET 10 4 MISC HEX SCREW 11 4 MISC 500 X 200 WASHER 12 1 33VF P8404 ODS ML 13 1 33VF P636si NOVASIT 820 14 1 33VF P112ve 1 5 X 375 NIPPLE 15 1 1000 257 E...

Страница 25: ...nel 10 1 1000 216 1000 216 Rocker Switch 11a 1 1000 214 1000 214 Piezo Igniter 11b 1 1000 215 1000 215 Pal Nut for Piezo Igniter 12 8 39GL 105 39GL 105 Grate Bar 13 1 350 P217SI 350 P217SI 1 1 2 On Of...

Страница 26: ...etal or tubing Keep igniter cable dry 5 Tighten nut 6 Replace igniter cable 7 Replace piezo igniter Remedy 1 Ventilate room Stop using odor causing products while heater is running 2 Locate and correc...

Страница 27: ...an burner or replace light burner ori ce 2 Replace burner ori ce 3 Contact quali ed service person Remedy 1 Contact local gas company 2 Clean burner or replace burner ori ce Remedy 1 Clean burner or r...

Страница 28: ...th service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoe...

Отзывы: