12
INSTALLING
INSTALLATION OF
GLMVF38/GLMVF40 INTO
EXISTING FIREPLACE
If installing in Canada or as a vented logset:
Appliance must be installed only in a solid fuel burning
fireplace with a working flue and constructed of non-
combustible material. See chart below for minimum per-
manent flue opening you must provide. The damper must
be secured so the minimum flue opening will be main-
tained at all times. This can be done by removing the
damper or welding the damper open.
Chimney Height
Minimum Permanent Flue
Opening
(feet)
(square inches)
6’ - 15’
39 square inches
15’ - 30’
29 square inches
Area of Various Standard Round Flues
Diameter (inside) Area (square inches)
5”
20 square inches
6”
29 square inches
7”
39 square inches
8”
51 square inches
The installation and the provisions for combustion and
ventilation air must conform with the National Fuel Gas
Code, ANSI Z223.1, or the CAN/CGA-B149, installation
codes
WARNING
Before installing in a solid fuel burning fireplace, the
chimney flue and firebox must be cleaned of soot,
creosote, ashes, and loose paint by a qualified chimney
cleaner. Creosote may ignite when heated to a high
temperature. Have chimney flue inspected for damage.
WARNING
Seal any fresh air vents or ash clean outdoors located
on the floor or wall of fireplace. If this is not done,
drafting may result causing pilot outage or sooting. Use
a heat-resistant sealant. Do not seal chimney flue
damper.
WARNING
This appliance is for installation in a solid-fuel burning
fireplace or approved ventless enclosure.
FIGURE 8 – Installing GLMVF38/GLMVF40 into existing fireplace.
WARNING
Installation of vented gas logs in the Commonwealth of
Massachusetts requires the vent damper be permanently
removed or welded in the full open position. Vented gas
logs can not be installed in a bedroom or bathroom in
the Commonwealth of Massachusetts.