MQZCVBG34 -Vented Chase Requirements
-
FIREPLACE CHASE MUST BE VENTED AT THE TOP OF THE ENCLOSURE.
•
Minimum
90 square inches
free air opening for grills (
V34EG
&
V34EGS
).
•
Minimum
2-1/4
” Gap
at top of enclosure for 3-Sided Open Top chases, and a
3” Gap
for Corner Installations.
Chase Vent Openings
LARGER
than the
required minimums
ARE
allowed and will reduce
surface temperatures. Must be flush with top of
enclosure.
HEAT CANNOT BE DISCHARGED INTO THE
WALLS, FLOOR, OR CEILING.
Heat must exit
through the required vented chase opening
near the ceiling.
ELECTRICAL WIRES IN CHASE MUST BE PROPERLY ATTACHED TO INSIDE
WALL OF CHASE. DO NOT RUN WIRES ABOVE APPLIANCE.
Please follow the current CSA C22.1 Canadian Electrical Code or the National
Electrical Code; ANSI/NFPA 70 when installed in the United States.
If using insulation in vented chase (i.e. for outside wall), wall board / drywall is required to support all insulation.
Vented chase must be clean and free of all debris (i.e. loose insulation, pieces of wood, etc.)
Vented Chase Opening Options:
Full Chase Options:
Recessed Chase Options:
LH or RH Corner Chase Options (Corner Kit Required):
Front Grill
Required
Optional Additional
Rear Grill- Must be in
the same Pressure
Zone (Room / Area)
Side Grills- Both
Sides of Chase
must be vented
Open Chase
Open Chase
Recessed
Front
Recessed Front
and Sides
Recessed Front
and Sides
2-
1/4”
2-
1/4”
2-
1/4”
3”
3”
3”
Optional Additional
Rear Grill- Must be in
the same Pressure
Zone (Room / Area)
Open Chase
Recessed
Front
Open Chase
Open Chase
Open Chase
Recessed
Front
Front Grill
Required
13
Содержание MQZCVBG34LPE2
Страница 58: ...Gas Conversion for Modulator PART C 58...
Страница 64: ...Proflame 2 Remote Control 64...
Страница 66: ...FAN OPTION NOT AVAILABLE 66...