5
Technical Information
Service Manual
Outdoor Unit
Model of Outdoor Unit
KW09HQ1B8DO
KW12HQ1B8DO
Outdoor Unit Product Code
CB427W02200_L74316
CB427W02100_L74316
Compressor Manufacturer/Trademark
ZHUHAI GREE DAIKIN DEVICE
CO.,LTD
ZHUHAI GREE DAIKIN DEVICE
CO.,LTD
Compressor Model
1GDY23AXD
1GDY23AXD
Compressor Oil
DAPHNE FVC50K
DAPHNE FVC50K
Compressor Type
Swing
Swing
Compressor Locked Rotor Amp (L.R.A)
A
/
/
Compressor RLA
A
6.6
6.6
Compressor Power Input
W
845
845
Overload Protector
KSD115
℃
or HPC115/95
KSD115
℃
or HPC115/95
Throttling Method
Capillary
Capillary
Operation temp
ºF
60.8~86
60.8~86
Ambient temp (cooling)
ºF
0~115
0~115
Ambient temp (heating)
ºF
-4~75
-4~75
Condenser Form
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube
Pipe Diameter
inch
Φ5/16
Φ5/16
Rows-fin Gap
inch
1-1/16
2-1/16
Coil Length (LXDXW)
inch
28X3/4X20
28X1 1/2X20
Fan Motor Speed
rpm
820
820
Output of Fan Motor
W
30
30
Fan Motor RLA
A
0.37
0.37
Fan Motor Capacitor
μF
2.5
2.5
Air Flow Volume of Outdoor Unit
CFM
942
942
Fan Type
Axial-flow
Axial-flow
Fan Diameter
inch
Φ15 3/4
Φ15 3/4
Defrosting Method
Automatic Defrosting
Automatic Defrosting
Climate Type
T1
T1
Isolation
I
I
Moisture Protection
IPX4
IPX4
Permissible Excessive Operating
Pressure for the Discharge Side
PSIG
550
550
Permissible Excessive Operating
Pressure for the Suction Side
PSIG
240
240
Sound Pressure Level (H/M/L)
dB (A)
52/-/-
53/-/-
Sound Power Level (H/M/L)
dB (A)
62/-/-
63/-/-
Dimension (WXHXD)
inch
30 9/16X21 1/4X12 5/8
30 9/16X21 1/4X12 5/8
Dimension of Carton Box (LXWXH)
inch
32 9/32X13 63/64X22 27/32
32 9/32X13 63/64X22 27/32
Dimension of Package (LXWXH)
inch
32 13/32X14 3/32X23 27/64
32 13/32X14 3/32X23 27/64
Net Weight
Ib
66.14
70.55
Gross Weight
Ib
71.65
76.06
Refrigerant
R410A
R410A
Refrigerant Charge
oz
24.7
30.0
Connection
Pipe
Length
ft
24.6
24.6
Gas Additional Charge
oz/ft
0.2
0.2
Outer Diameter Liquid Pipe
inch
Φ1/4
Φ1/4
Outer Diameter Gas Pipe
inch
Φ3/8
Φ3/8
Max Distance Height
ft
32.8
32.8
Max Distance Length
ft
49.2
65.6
Note:The connection pipe applies metric diameter.
The above data is subject to change without notice. Please refer to the nameplate of the unit.