Installation and Maintenance
Service Manual
39
Anti-freezing
protection for
evaporator
E2
Not the error code. It’s
the status code for the
operation.
40
Cold air
prevention
protection
E9
Not the error code. It’s
the status code for the
operation.
41
Refrigerant
recovery
mode
Fo
Refrigerant recovery. The
Serviceman operates it
for maintenance.
42
Undefined
outdoor unit
error
oE
Cool: compressor
and outdoor fan stops
operation, while indoor
fan operates; Heat:
compressor, outdoor
fan and indoor fan stop
operation.
1. Outdoor ambient
temperature exceeds
the operation range of
unit (eg: less than-20oC
or more than 60oC for
cooling; more than 30oC
for heating);
2. Failure startup of
compressor?
3. Are wires of
compressor not
connected tightly?
4. Is compressor
damaged?
5. Is main board
damaged?