Page 33 of 39
King Pigeon Hi-Tech. Co., Ltd.
Ver 1.0
GSM/SMS/GPRS/3G/4G/Ethernet/Cloud
LoRa Gateway
Appendix A :SMS Commands
The SMS commands will be used for remote control the RTU as below, SMS Commands must be
CAP Locks
:
1
)Commands error return SMS
2)External DC Status
3)External DC Power Lost Delay Time to Alarm
4)Modify Password, 4digits, default is 1234
SMS Command
Return SMS Content
Old Password
+
P
+
New Password
This is the New Password, please remember it carefully.
5)Set Device ID Number
SMS Command
Return SMS Content
Set
p IDxxxxx
xxxxx=1~65535. Default is 1.
ID:XXXXX
query
pIDE
ID:XXXXX
6
)
Set Gateway Time
Format is 2015-05-22 15:20:30W01, the W01 stands for Monday, W07 stands for Sunday.
Event
Return SMS Content
Any incorrect Command
SMS Format Error, Please check Caps Lock in Command!
Event
Return SMS Content
External DC goes off
External DC Power Goes OFF
SMS Command
Return SMS Content
Set
pACxxx
xxx stands for delay time, range
000~999 minutes. =000, stands for
alarm immediately, =999 stands for DC
power lost will not alarm. Default is
000.
External DC Power Lost Delay time to Alarm: xxx minutes
query
pAC
External DC Power Lost Delay time to Alarm: xxx minutes
SMS Command