channel is humidity.
◆
Channel name:
It is filled in according to the way of use, and the terminal alarm is used when
sending text messages. The content can be up to 40 bytes in length.
◆
Maximum minimum:
fixed, temperature measurement range: -40-80
℃
, humidity measurement
range: 0-99% RH. This can be ignored by the user during configuration.
◆
High Threshold alarm value
: the current value of the channel exceeds this value and is considered
as the high limit alarm.
◆
Low Threshold alarm value
: the current value of the channel is lower than this value and is
considered as the low limit alarm.
◆
High-Threshold alarm SMS content, low-Threshold alarm SMS content, recovery SMS content:
alarm and recovery, send SMS content to customers, each SMS content length supports 40 contents. The
default is: high limit alarm, low limit alarm, recovery.
◆
Enable Recovery SMS :
When device alarm status is restored, set the device sends a recovery SMS
or not.
Configure LoRa Slave
Steps:
1.Power on slave device,it will stay in pre-configuration mode for 10seconds,signal light keeps on.
2.During pre-configuration mode,click “save WT100 Settings”.
3.If slave’s signal light off,means not receive configuration data.
4.If configuration data is updated,signal light will be on for 1s,then off ,and enter working mode
with new configuration data.
Note:When configure WT104/WT105/WT106 not successfully,and need re-configure, must power off
WT104/WT105/WT106 and
wait for 20s,then can power on and configure.Because the device has very low
power-consumption ,after power off device,still need wait 20s till power on PCB is used up.
”Slave Management” is mainly for WT104 /WT105configuration and current value.WT100 slave is data
transparent transmission,so “slave management” no WT100.
Load and export slave WT104/WT105/WT106 configuration information
If you needs to write the current WT104 parameter in other slave device(same model) , you can use these
two buttons to copy and save settings of device configuration.
3.7.4 Add WT100
(
RS485 Transparent transparent transmission slave device
)
Follow the steps below to add the WT100 slave terminal device.
1)
Select the working frequency,and save gateway setting.
2
)Fill in the configuration information of WT100 on the configuration software
◆
Slave serial NO:
Device address of the terminal (range: 1-100)
◆
Baud rate:
1200-115200 is optional, choose according to the actual situation, default: 9600. ,