Page 22
9. Other functions
9.c- Modification of Modbus communication speed
Go into configuration mode (see page 5). The folder number displayed
corresponds to the last configuration folder used.
Select the folder “
100
” and validate with
.
Select the sub-folder “
104
” and validate with
.
The cursor
>
returns to sub-folders line.
• press twice
to return to reading mode.
• press once
to return to another folder selection.
• with
and
keys, you can choose another sub-folder from the folder 100.
dbu
o
s
M
208
With
and
keys, select a communication speed
(see chart below). Validate with
.
00
2400 bauds
03
19200 bauds
01
4800 bauds
04
38400 bauds
02
9600 bauds
05
115200 bauds
(speed by default)
1
Step
2
Step
3
Step
4
Step
CPE 300 transmitter configuration via remote control / Modbus
1
Step
2
Step
3
Step
4
Step
9.d- Purge mode
Go into configuration mode (see page 5). The folder number displayed
corresponds to the last configuration folder used.
Select the folder “
300
” and validate with
.
Select the sub-folder “
306
” and validate with
.
The cursor
>
returns to sub-folders line.
• press twice
to return to reading mode.
• press once
to return to another folder selection.
• with
and
keys, choose another sub-folder from the folder 300
dbu
o
s
M
612
With
and
keys, activate (
01
) or deactivate (
00
) the purge
mode. Validate with
.
The purge mode enables to freeze the measurement when being displayed, enables to lock the analogue outputs,
and to activate the relay 1, in order to actuate a de-dust system of a air movement conditions.
9.d.1 -Activation / deactivation of Purge Mode
Содержание CPE 300
Страница 2: ......
Страница 30: ...NOTES Page 25 CPE 300 transmitter configuration via remote control Modbus...
Страница 31: ...NOTES Page 26 CPE 300 transmitter configuration via remote control Modbus...