6.a.2 - Output diagnostics
Once the connection of the transmitter to the multimeter (or regulator or PLC/BMS is complete, (see page
8), you can carry out the analogue output diagnostics on several check points.
6. Analogue output management
Go into configuration mode (see page 5). The folder number displayed
corresponds to the last configuration folder used.
Select the folder “
300
” and validate twice with
.
The cursor
>
goes to available choices.
Diagnostic Output
00
0 V
01
5 V
02
10 V
03
4 mA
04
12 mA
05
20 mA
With
and
keys, select the signal that the transmitter must output (see chart
below). Note : no need to validate with
.
!
If the deviations are too large
(>0,05V or >0,05mA) between the signal issued and the
value displayed on the multimeter,
we recommend that you return the transmitter to
our factory.
The cursor
>
returns to sub-folders line.
• press twice
to return to reading mode.
• press once
to return to another folder selection.
• with
and
keys to choose another sub-folder from the folder 300.