7.f - Setpoints and time-delay setting
7. Alarm / relay settings
Go into configuration mode (see page 5). The folder number displayed
corresponds to the last configuration folder used.
Select the folder “
400
” and validate with
.
With
and
keys, select the setpoint value and validate with
.
Note : the left column can be either a integer (from 0 to 9) or a negative sign
for a negative setpoint.
The cursor
>
returns to sub-folders line.
• press twice
to return to reading mode.
• press once
to return to another folder selection.
• with
and
keys, you can choose another sub-folder from the folder 400.
7.f.1 - Setpoints
!
You must enter values according to the units of measurement selected, not
according to the measuring range of the transmitter.
Ex.
on a CP 303 pressure transmitter (0 to ±1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must be
configured on measuring range of 0 to ±102 mmH2O.
See conversion chart on page 11.
If after having set up a setpoint, the unit of measurement is modified (see page 9), then you have to reconfigure
the setpoints according to this new unit of measurement.
“403”
“407”
“411”
“415”
Alarm
1
Alarm
2
Relay
1
Relay
2
To configure the
setpoint 1
,
select sub-folder
and validate with
.
dbu
o
s
M
806
dbu
o
s
M
814
dbu
o
s
M
822
dbu
o
s
M
830
“404”
“408”
“412”
“416”
Alarm
1
Alarm
2
Relay
1
Relay
2
To configure the
setpoint 2
b-folder
(alarm in
control mode,
see p17)
,
select su
and validate with
.
dbu
o
s
M
808
dbu
o
s
M
816
dbu
o
s
M
824
dbu
o
s
M
832
1
Step
2
Step
3
Step
4
Step
Page 17
CPE 300 transmitter configuration via remote control / Modbus