Kimo CPE 300 Скачать руководство пользователя страница 1

Flush-mount transmitter

CPE 300

MODBUS system

MODBUS system

MODBUS system

Remote control

Remote control

Remote control

w

e

N w

e

N

w

e

N w

e

N

User Manual

Pressure • Temperature • Humidity • Air Velocity • Air Flow

Содержание CPE 300

Страница 1: ...sh mount transmitter CPE 300 MODBUS system MODBUS system MODBUS system Remote control Remote control Remote control w e N w e N w e N w e N User Manual Pressure Temperature Humidity Air Velocity Air F...

Страница 2: ......

Страница 3: ...7 Alarm Relay settings F400 P 12 7 a Activation Deactivation of BEEP alarm P 12 7 b Relay security P 12 7 c Alarm relay functions and LED colour codes P 13 7 d Alarm mode details P 14 7 e Alarm mode...

Страница 4: ...lcode fulldetailsinthismanual Visual alarm LED Alphanumeric display infrared receiver Meaning of the keys To increment a value or a level To decrement a value or a level To validate an input To cancel...

Страница 5: ...signal Voltage or Current Down 4 20 mA Up 0 10 V 1 b Output signal selection With the on off switch located on the left top of the transmitter when open you can choose analogue output 0 10V voltage or...

Страница 6: ...by the transmitter is 5 Alarm condition 1 and relay 1 energized Values Modbus code 1438 channel 1 1442 value 1 for the external transmitter 1446 value 2 for the external transmitter Ex the value sent...

Страница 7: ...to Registers Serial number of SPI sensing element Modbus code 1402 Other access codes to different registers are indicated on each function at stage n 2 Shown as this pictogram dbu o s M 200 CPE 300 t...

Страница 8: ...this column is activated and you can enterdatafromthekeypad This screen appears Step 3 This screen confirms that the code was correctly entered and that you can configurethetransmitter If the code wa...

Страница 9: ...de press once to select another folder with and keys you can choose another sub folder from the folder dbu o s M 200 By default the channel number is 0 Page 6 4 b Slave addressing Modbus Go into confi...

Страница 10: ...hoices line With and keys select the unit of measurement see chart below Validate with The cursor returns to sub folders line press twice to return to reading mode press once to return to another fold...

Страница 11: ...meter connection configuration Before carrying out the output diagnostics all connections and configurations of the transmitter must be enabled toavoidanydamageonthetransmitterandthemultimeter Example...

Страница 12: ...t 00 0 V 01 5 V 02 10 V 03 4 mA 04 12 mA 05 20 mA With and keys select the signal that the transmitter must output see chart below Note noneedtovalidatewith If the deviations are too large 0 05V or 0...

Страница 13: ...E 303 pressure transmitter 0 to 1000 Pa with a reading in mmH2O the minimum and maximum ranges must be configured on measuring range of 0 to 102 mmH2O See conversion chart on following page 6 Step The...

Страница 14: ...nalogue output management Page 11 Pa mmH2O inWg mbar CPE 301 0 to 100 0 to 10 2 1 00 CPE 302 0 to 0 to 0 0 to 01 0 to 00 CPE 303 0 to 1000 0 to 0 to 0 to 0 40 0 to 500 51 2 5 0 to 102 0 4 02 10 00 CPE...

Страница 15: ...nd validate with Select sub folder 401 and validate with The cursor goes to available choices With the keys and select 01 for a positive security or 00 for a negative security Validate with The cursor...

Страница 16: ...eached Red The alarm function is activated and the setpoint is reached None The alarm function is not activated The red LED appears when the setpoint is reached taking into account the time delay and...

Страница 17: ...singaction thealarmisactivatedoncethemeasurementgoesoverthesetpoint Fallingaction thealarmisactivatedoncethemeasurementgoesbelowthesetpoint 7 d 2 Available configurations Seuil 1 Seuil 2 Temps Measure...

Страница 18: ...ed Not energized Relay status Positivee security T T T T Alarm set Time delay Configuration N 3 1 setpoint time delay and falling action activated Setpoint 1 Time Measurement Energized Not energized R...

Страница 19: ...ss once to return to another folder selection with and keys you can choose another sub folder from the folder 400 Code Mode d alarme Schema 00 No alarm 01 2 setpoints with time delay control mode N 1...

Страница 20: ...ingtothemeasuringrangeofthetransmitter Ex on a CP 303 pressure transmitter 0 to 1000 Pa with a reading in mmH2O the minimum and maximum ranges must be configured on measuring range of 0 to 102 mmH2O S...

Страница 21: ...time delay enter 00 Validatewith The cursor returns to sub folders line press twice to return to reading mode press once to return to another folder selection with and keys youcanchooseanothersub fold...

Страница 22: ...Coef xN Value Coef xformervalue Newvaluedisplayed 10 This value is applicable when the variation is less than Coef x 10 Pa Go into configuration mode see page 5 The folder number displayed corresponds...

Страница 23: ...tions from 0 to 60minutes Validate with Note ifthevalueis equalto 0 thetransmitterwillnot carryoutanyself calibration dbu o s M 1002 The cursor returns to sub folder line press twice to return to read...

Страница 24: ...return to reading mode press once to return to another folder selection with and keys youcanchooseanothersub folderfromthefolder100 9 b Serial number display Go into configuration mode see page 5 The...

Страница 25: ...y default 1 Step 2 Step 3 Step 4 Step CPE 300 transmitter configuration via remote control Modbus 1 Step 2 Step 3 Step 4 Step 9 d Purge mode Go into configuration mode see page 5 The folder number dis...

Страница 26: ...60 Validate with 9 d 2 Working duration of purge mode dbu o s M 614 1 Step 2 Step 3 Step 4 Step 1 Step 2 Step 3 Step 4 Step Page 23 CPE 300 transmitter configuration via remote control Modbus Go into...

Страница 27: ...ion with and keys choose another sub folder from the folder 300 dbu o s M 618 With and keys enter the value in seconds of the time delay required from00to60 Validatewith Once the purge is finished tim...

Страница 28: ...308 Frequency of each purge from 01 to 9999 minutes 309 Time delay after purge from 00 to 60 seconds dbu o s M xxx Code Description Available settings 500 0 to 9 1000 1002 Measurement integration from...

Страница 29: ...of alarm 2 409 Time delay on alarm 2 from 0 to 60 seconds 410 Alarm type selection for Relay 1 0 inactive 1 setpoint 1 setpoint 2 and time delay 2 setpoint 1 time delay and rising action 3 setpoint 1...

Страница 30: ...NOTES Page 25 CPE 300 transmitter configuration via remote control Modbus...

Страница 31: ...NOTES Page 26 CPE 300 transmitter configuration via remote control Modbus...

Страница 32: ...Ref NT ang CPE300 02 07 B We reserve the right to modify the characteristics of our products without notice...