9.3.
F 300 : Manage the analogue inputs
Code
Register type
Modbus
Description
Possibilities
F 300
Enumeration*
3000
Channel 1 analogue input
selection
4-20 mA / 0-20 mA / 0-10 V / 0-5 V / 0-2.5 V
F 310
Enumeration*
3100
Channel 2 analogue input
selection
4-20 mA / 0-20 mA / 0-10 V / 0-5 V / 0-2.5 V
F 320
Enumeration*
3200
Channel 3 analogue input
selection
4-20 mA / 0-20 mA / 0-10 V / 0-5 V / 0-2.5 V
F 301
Real
3010
Channel 1 minimum range
From -9.99 to 99.99 and from -999 to +999
F 302
Real
3020
Channel 1 maximum range
From -9.99 to 99.99 and from -999 to +999
F 304
Enumeration
3030
Channel 1 decimal point
position
0, 1, 2, 3 or 4
F 311
Real
3110
Channel 2 minimum range
From -9.99 to 99.99 and from -999 to +999
F 312
Real
3120
Channel 2 maximum range
From -9.99 to 99.99 and from -999 to +999
F 314
Enumeration*
3030
Channel 2 decimal point
position
0, 1, 2, 3 or 4
F 321
Real
3210
Channel 3 minimum range
From -9.99 to 99.99 and from -999 to +999
F 322
Real
3220
Channel 3 maximum range
From -9.99 to 99.99 and from -999 to +999
F 324
Enumeration*
3030
Channel 3 decimal point
position
0, 1, 2, 3 or 4
9.4.
F 400 : Manage the alarms
Code
Register type
Modbus
Description
Possibilities
F 400
Enumeration*
4000
Alarm mode of the alarm 1 OFF: None
1/3 : Rising edge
2/3 : Falling edge
3/3 : Monitoring
F 401
U8
4010
Alarm 1 channel selection
Channel 1
Channel 2
Channel 3
F 402
Real
4020
Threshold setting of the
alarm 1
According to the channel to display
F 403
Real
4030
Threshold 2 or hysteresis
setting of the alarm 1
According to the channel to display
F 404
U16
4040
Time-delay 1 alarm 1
setting
From 0 to 600 s
F 405
U16
4050
Time-delay 2 alarm 1
setting
From 0 to 600 s
F 406
Boolean
4080
Audible alarm 1
0 : activated / 1 : deactivated
F 407
U8
4070
Alarm 1 acknowledgement
duration
From 0 to 60 minutes
See Enumeration table page 8