Code
Register type
Modbus
Description
Possibilities
F 410
Enumeration*
4100
Alarm mode of the alarm 2 OFF: None
1/3 : Rising edge
2/3 : Falling edge
3/3 : Monitoring
F 411
U8
4110
Alarm 2 channel selection
Channel 1
Channel 2
Channel 3
F 412
Real
4120
Threshold 1 setting of the
alarm 2
According to the channel to display
F 413
Real
4130
Threshold 2 or hysteresis
setting of the alarm 2
According to the channel to display
F 414
U16
4140
Time-delay 1 alarm 2
setting
From 0 to 600 s
F 415
U16
4150
Time-delay 2 alarm 2
setting
From 0 to 600 s
F 416
Boolean
4180
Audible alarm 2
1 : activated / 0 : deactivated
F 417
U8
4170
Alarm 2 acknowledgement
duration
From 0 to 60 minutes
F 420
Enumeration*
4200
Alarm mode of the alarm 3 OFF: None
1/3 : Rising edge
2/3 : Falling edge
3/3 : Monitoring
F 421
U8
4210
Alarm 3 channel selection
Channel 1
Channel 2
Channel 3
F 422
Real
4220
Threshold 1 setting of the
alarm 3
According to the channel to display
F 423
Real
4230
Threshold 2 or hysteresis
setting of the alarm 3
According to the channel to display
F 424
U16
4240
Time-delay 1 alarm 3
setting
From 0 to 600 s
F 425
U16
4250
Time-delay 2 alarm 3
setting
From 0 to 600 s
F 426
Boolean
4280
Audible alarm 3
1 : activated / 0 : deactivated
F 427
U8
4270
Alarm 3 acknowledgement
duration
From 0 to 60 minutes
*See Enumeration table page 8
Functions recap and Modbus connections
22