Kimo 210-R Series Скачать руководство пользователя страница 8

3.  ACCESS TO THE DIFFERENT FUNCTIONS

This step is compulsory for each configuration.

First, to access to the transmitter functions, and for safety, a safety code must be entered. This safety code is 

0101 

and 

can

not be modified

.

The transmitter must be energised.

Connect the transmitter.

Wait for the initialisation phase.

Press 

OK

.

The screen displays 

“Code” 

with 

“0000”

. The first 0 blinks.

Press 

OK

 to go to the second 0.

It blinks.

Press 

Up

 key to display 1 then press 

OK

.

The third 0 blinks.

Press 

OK

 to go to the fourth 0.

Press 

Up

 key to display 1 then press 

OK

.

The following screen is displayed: 

“F 100” 

is for the number of the configuration folder. There are 6 folders:

F 100:

 folder of the transmitter configuration. See page 9

F 200: 

folder of the channels and units of measurement. See page 11

F 300:

 folder of the analogue outputs. See page 12

F 400: 

folder of the relays configuration. See page 16

F 500: 

folder of the measurement configuration. See page 18

F 600: 

folder of the measurement configuration specific to the COT212-R, CP210-R and CTV210-R transmitters.

See page 21

To select the required folder: 

“F 100” 

is displayed and 1 is blinking.

Press 

Up

 key until the number of the required folder is display (

“F 100”, “F 200”, “F 300”, “F 400”, “F 500”

or 

“F 600”

 according to the type of transmitter).

Press 

OK

.

If a wrong code is entered, “CODE” blinks a few seconds on the bottom right of the screen then
the measured values are displayed. It is necessary to enter the right code.

8

ACCESS TO THE DIFFERENT FUNCTIONS

F    100

Code

0101

Содержание 210-R Series

Страница 1: ...Configuration of class 210 R transmitters by keypad USER MANUAL...

Страница 2: ......

Страница 3: ...R 18 8 2 Pressure measurement integration CP210 R 18 8 3 Time delay between two auto zeros CP211 R and CP212 R 18 8 4 Air velocity measurement integration CTV210 R 19 8 5 Add an offset 19 9 F 600 COMP...

Страница 4: ......

Страница 5: ...a moving average on the last hour M1 to compare with a moving average on the last 5 minutes M2 If M1 M2 the trend is stable If M1 M2 the trend is upwards If M1 M2 the trend is downwards Indicator ligh...

Страница 6: ...0 V 0 5 V 0 20 mA Combinations 1 4 Protection tip of the sensors It s extremely unwise to remove the protection tip of our hygrometry probes as the sensitive element is very fragile even to light cont...

Страница 7: ...nge to place in the cable gland must be between 4 and 8 mm The power supply wiring must be performed with crimping copper connections or a tinning in case of multi wire cable After performing the wiri...

Страница 8: ...6 folders F 100 folder of the transmitter configuration See page 9 F 200 folder of the channels and units of measurement See page 11 F 300 folder of the analogue outputs See page 12 F 400 folder of th...

Страница 9: ...blinks Set it between 0 and 5 pressing Up and Down keys When pressing Up or Down key to change the contrast level there is a lag time of 1 second where the digits disappear then they reappear with the...

Страница 10: ...splayed Press Up key F 140 is displayed with OFF meaning that the locking is deactivated Press OK OFF blinks Press Up or Down key ON blinks then press OK LOCK is displayed for a few seconds then the t...

Страница 11: ...n key to select the sub folder F 210 corresponding to the channel 2 Press Up and Down keys to select the required unit according to the type of transmitter sign allows to deactivate the channel Units...

Страница 12: ...onfiguration Before carrying out the output diagnostics all connections and configurations of the transmitter must be enabled to avoid any damage on the transmitter and the measurement device Select a...

Страница 13: ...e transmitter is powered on Press OK Enter the activation code see page 8 Press OK Press Up key to go to folder F 302 corresponding to the low range of the channel 1 Press OK The first digit of the lo...

Страница 14: ...ork to clean the installation 6 Purge duration for example 30 seconds 7 Deactivation of the relay 1 stop sending compressed air 8 Wait for time delay for example 10 seconds 9 Deactivation of the relay...

Страница 15: ...mmHG kPa PSI daPa hPa CP211 R 100 10 2 0 40 1 00 0 75 0 100 10 0 1 00 CP212 R 1000 102 0 4 01 10 00 7 50 1 000 100 0 10 00 CP213 R 10 000 1019 7 40 14 100 00 75 00 10 000 1000 0 100 00 Temperature TH2...

Страница 16: ...nds to the relay 2 setting The relay setting procedure explained below corresponds to the relay 1 setting For the relay 2 setting go to the corresponding folder and perform the same procedure as for t...

Страница 17: ...digit has been set F 403 blinks Press Up key to go to the F 404 folder F 414 for relay 2 then press OK This folder corresponds to the delay 1 setting Set the delay 1 with the Up and Down keys Press O...

Страница 18: ...to pressure changes When making measurements in unstable air movement conditions the pressure measurement may fluctuate The integration coefficient from 0 to 9 makes an average of the measurements th...

Страница 19: ...nstable the user selects a strong integration Integration 7 The variation is lower than 10 m s it is possible to apply the integration calculation formula Next displayed value 2 8 7 2 10 3 m s The tra...

Страница 20: ...value then press OK The second number blinks Enter with Up and Down keys its value then press OK Repeat the procedure for the following numbers Press OK when the last number is set F 531 blinks the of...

Страница 21: ...nks Press Up or Down key to set the temperature sign 0 for a positive temperature or for a negative temperature Press OK The 2nd digit blinks Press Up or Down key to set the digit then press OK Repeat...

Страница 22: ...210 R The transmitter is powered on Press OK Enter the activation code see page 8 Press OK Press Up key to go to F 611 folder Press OK Set the 1st digit with Up and Down keys then press OK to set the...

Страница 23: ...ar section The transmitter is powered on Press OK Enter the activation code see page 8 Press OK Press Up key to go to F 622 folder to set the length of the rectangular section Press OK Set the length...

Страница 24: ...e airflow Airflow C D pressure The transmitter is powered on Press OK Enter the activation code see page 8 Press OK Press Up key to go to F 625 folder to set the coefficient value Press OK Set the coe...

Страница 25: ...2 deactivation of the channel According to the type of transmitter see below Units available according to the channel and the type of transmitter CP211 212 213 R Pa mmH2O inWG mbar mmHg daPa kPa hPa...

Страница 26: ...V 10 mA 12 mA 3 10 V 5 V 20 mA 20 mA F 312 Low range of the channel 2 According to the type of transmitter F 313 High range of the channel 2 According to the type of transmitter F 390 Purge mode ON a...

Страница 27: ...the measurement pressure From 0 to 9 F 501 CTV210 R only Integration of the measurement air velocity From 0 to 9 F 510 CP210 R with solenoid valve only Time delay between two auto calibrations From 0...

Страница 28: ...the section 0 mm 1 inch F 622 CP210 R and CTV210 R Rectangular section length F 623 CP210 R and CTV210 R Rectangular section width F 624 CP210 R and CTV210 R Circular section diameter F 625 CP210 R Ai...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...NTang Transmitters_Class_210 R 30 10 18 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice...

Отзывы: