10.3. F 300
Code
Description
Possibilities
F 301
Diagnostic of the channel 1:
generation of current or voltage
Display
Generation according to the output
signal
0-10 V
0-5 V
0-20 mA 4-20 mA
0
no generation
1
0 V
0 V
0 mA
4 mA
2
5 V
2.5 V
10 mA
12 mA
3
10 V
5 V
20 mA
20 mA
F 302
Low range of the channel 1
According to the type of transmitter
F 303
High range of the channel 1
According to the type of transmitter
F 311
Diagnostic of the channel 2:
generation of current or voltage
Display
Generation according to the output
signal
0-10 V
0-5 V
0-20 mA 4-20 mA
0
no generation
1
0 V
0 V
0 mA
4 mA
2
5 V
2.5 V
10 mA
12 mA
3
10 V
5 V
20 mA
20 mA
F 312
Low range of the channel 2
According to the type of transmitter
F 313
High range of the channel 2
According to the type of transmitter
F 390
Purge mode
ON: activated
OFF: deactivated
F 391
Purge duration
From 1 to 60 seconds
F 392
Duration between two purges
From 1 to 9999 minutes
F 393
Delay
From 1 to 60 seconds
10.4. F 400
Code
Description
Possibilities
F 400
Activation mode of relay 1
0: None
1: Rising edge
2: Falling edge
3: Monitoring
F 401
Channel selection relay 1
Channel 1
Channel 2
F 402
Threshold 1 relay 1 setting
According to the connected probe
F 403
Threshold 2 or hysteresis relay 1 setting
According to the connected probe
F 404
Delay 1 relay 1 setting
From 0 to 600 seconds
F 405
Delay 2 relay 1 setting
From 0 to 600 seconds
26