Screen
Generated output
Example
0
Deactivated
-
1
Simulates 0% of the output range
On the 0-10V range, the transmitter will generate 0V.
2
Simulates 50% of the output range On the 0-10V range, the transmitter will generate 5V.
3
Simulates 100% of the output range On the 0-10V range, the transmitter will generate 10V.
If the deviations are too large (> 0.05V or > 0.05mA) between the signal issued and the value
displayed on the multimeter, we recommend to return the transmitter to our factory.
➢
For the diagnostic of the
channel 2
, go to
“F 311”
folder and do the same procedure as the channel 1.
6.2. Set the range of the analogue outputs
This function allows to modify the range of the analogue outputs.
Values to enter depend on the measurement unit and not on the measurement range of the
transmitter.
Ex: on a CP211-R pressure transmitter (0 to ±1000 Pa) with a reading in mmH
2
O, the minimum and maximum ranges must
be configured on measuring range of 0 to ±102 mmH
2
O.
See conversion chart on page 15.
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code
(see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to folder
“F 302”
corresponding to the low range of the channel 1.
➢
Press
OK
.
The first digit of the low range blinks.
➢
Enter with
Up
and
Down
keys the figure value or the negative sign of the value then press
OK
.
The second digit blinks.
➢
Enter with
Up
and
Down
keys its value then press
OK
.
➢
Perform the same procedure for the following figures.
➢
Press
OK
when the last figure has been configured.
“F 302”
blinks, the low range is configured.
➢
Press
Up
key then press
OK
to enter in the folder
“F 303”
corresponding to the high range of the channel 1.
The first digit of the high range blinks.
➢
Enter with
Up
and
Down
keys the figure value or the negative sign of the value then press
OK
.
The second digit blinks.
➢
Enter with
Up
and
Down
keys its value then press
OK
.
➢
Perform the same procedure for the following figures.
➢
Press
OK
when the last figure has been configured.
“F 303”
blinks, the high range is configured.
To set the low and high ranges of the channel 2, go to the folders “F 312” (low range) and “F 313”
(high range) and follow the setting procedure of the channel 1.
F 300: ANALOGUE OUTPUTS MANAGEMENT
13