9. F 600: COMPENSATION, MEANS OF MEASUREMENT AND
SECTION SETTINGS
9.1. Temperature compensation (CP210-R)
It is possible to modify the temperature compensation. Indeed the air velocity and airflow measured with a differential
probe (such as Pitot tube, Debimo blade, orifice plate...) depends on the working temperature. Then, it is required to enter
the
working temperature
to get more accurate results.
9.1.1 Set the unit
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 600”
folder.
➢
Press
OK
.
➢
Select
0
for °C or
1
for °F then press
OK
.
9.1.2 Set the temperature compensation value temperature
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 602”
folder.
➢
Press
OK
.
The 1
st
digit blinks.
➢
Press
Up
or
Down
key to set the temperature sign:
0
for
a positive temperature
or
–
for a
negative
temperature.
➢
Press
OK
.
The 2
nd
digit blinks.
➢
Press
Up
or
Down
key to set the digit then press
OK
.
➢
Repeat the procedure for the following digits.
➢
Press
OK
when the last digit has been set to validate the temperature compensation value.
9.2. Altitude compensation (COT212-R, CP210-R and CTV210-R)
If measurements are performed at a specific altitude, it is advised to set the altitude in which the transmitter is.
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 605”
folder.
➢
Press
OK
.
The 1
st
digit blinks.
➢
Press
Up
or
Down
to set the digit:
only 1 and 0 are available.
➢
Press
OK
.
The 2
nd
digit blinks.
➢
Press
Up
and
Down
key to set the digit then press
OK
.
➢
Repeat the procedure to set the following digits.
➢
Press
OK
when the last digit has been set to validate the altitude value.
F 600: COMPENSATION, MEANS OF MEASUREMENT AND SECTION SETTINGS
21