9.4. Setting of the type of section and airflow coefficient (CP210-R, CTV210-R)
This function is available for CP210-R transmitters with SQR3 option only.
9.4.1 Select the type of section
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 620”
folder.
➢
Press
OK
.
➢
Select
0, 1, or 2
for:
➢
0:
rectangular section
➢
1:
circular section
➢
2:
coefficient*
9.4.2 Select the unit of the section
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 621”
folder.
➢
Press
OK
.
➢
Select
0
or
1
for:
➢
0:
section in mm
➢
1:
section in inch
9.4.3 Set the size of the section
For a rectangular section:
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 622”
folder to set
the length of the rectangular section
.
➢
Press
OK
.
➢
Set the length with
Up
and
Down
keys.
➢
Press
OK
when the last digit has been set to validate the length.
➢
Press
Up
key to go to
“F 623”
folder to set
the width of the rectangular section
➢
Press
OK
.
➢
Set the width with
Up
and
Down
keys.
➢
Press
OK
when the last digit has been set to validate the width.
For a circular section:
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation code (see page 8).
➢
Press
OK
.
➢
Press
Up
key to go to
“F 624”
folder to set the diameter of the circular section.
➢
Press
OK
.
➢
Set the diameter with
Up
and
Down
keys.
➢
Press
OK
when the last digit has been set to validate the diameter.
F 600: COMPENSATION, MEANS OF MEASUREMENT AND SECTION SETTINGS
23
*CP210-R only.