![Kilowatt Labs CENTAURI ENERGY SERVER Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/kilowatt-labs/centauri-energy-server/centauri-energy-server_user-manual_1967130034.webp)
Centauri Energy Server
–
User Manual
Model Number - GF-20000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
34
and click the
“
”
to confirm the operation. (C for battery capacity, the system will calculate the
standard charging current based on the total capacity of the battery, with the system default for (0.15
C x 100 AH = 15 A).
•
Setup of Battery Type (Reserved option):
Click the
“
BAT TYPE
”
button to select
“
LEAD
”
or
“
LITH
”
option and then confirm the operation by
pressing button.
•
Setup of Quantity of Batteries (Fine-tuning setup):
Click the
“
BAT CELL
”
to enter the corresponding setting interface, and then input the standard quantity
of the batteries used in this system (Base on the standard of 2V unit batteries, the standard quantity
of batteries for this system is 180, with the maximum set value of 166-182) and then press
“
YES
”
button to confirm the operation.
•
Setup of Temperature Configuration:
Click on
“
TEMPCMP
”
button to enter the corresponding setting interface (The default setting of the
system is 2 mV, but the engineers can choose the appropriate parameter according to the
requirements of the battery characteristics), and then click
“
YES
”
button to confirm the operation
(without the temperature sensor, the system will conduct the ambient temperature compensation).
•
Setup of DOD (depth of discharge):
Click
“
DOD
”
and enter setting interface. This value is for power supply priority transfer point, battery
end of testing point and battery low voltage alarm point. System default value is 1.89V and set range
is 1.85-2.1 V. Click
“
”
to activate.
•
Setup of EOD (end of discharge):
Click
“
EOD
”
and enter setting interface. System default value is 1.75V and set range is 1.58-1.83V. Click
“
”
to activate.
5.5.1.4 Password Setting:
•
Operation method:
→
Click the
“
OPEN SET
”
button to enter the corresponding setting interface.
→
Click
“
Password Lock
”
button, the system will display
“L
OCK PWD
”
Information.
→
C
lick the button again, the system will display “OPEN” or “CLOSE”
information.
→
Click the
“
YES
”
button to confirm the setting.