![Kilowatt Labs CENTAURI ENERGY SERVER Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/kilowatt-labs/centauri-energy-server/centauri-energy-server_user-manual_1967130025.webp)
Centauri Energy Server
–
User Manual
Model Number - GF-20000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
25
4.9 Power Cable:
While choosing suitable external cables for connection, the following factors should be taken into
account:
i.
Current capacity of power cable
ii.
Requirements of the system overload capacity
iii.
The ambient temperature
iv.
Physical support media
The qualified installation engineers should select suitable cable for connection according to local
related standards and table 9. The length of the cables should be limited to 2-10 meters because too
long cable can lead to the low voltage otherwise, the cross-section area of the corresponding cable
should be increased.
Rated
Capacity
(KVA)
Standards
10
20
30
40
50
60
80
100
120
Bypass
input cable
Max Current (A)
22
44
66
88
111
133
177
222
266
National
Standard (mm2)
≥4
≥10
≥16
≥25
≥35
≥50
≥70
≥70
≥95
American
Standard (AWG)
≥12
≥6
≥4
≥2
≥1
≥0
≥000
≥000
≥0000
AC input
cable
Max Current (A)
35
70
105
140
175
210
280
350
415
National
Standard (mm2)
≥8
≥16
≥25
≥35
≥50
≥70
≥70
≥95
≥120
American
Standard (AWG)
≥8
≥4
≥2
≥1
≥0
≥000
≥000
≥000
0
≥250
kcmil
Output
cable area
Max Current (A)
22
44
66
88
111
133
177
222
266
National
Standard (mm2)
≥4
≥10
≥16
≥25
≥35
≥50
≥70
≥70
≥95