American
Standard (AWG)
≥12
≥6
≥4
≥2
≥1
≥0
≥000
≥000
≥0000
Battery
input cable
Max Current (A)
34
68
102
137
171
205
274
342
411
National
Standard (mm2)
≥6
≥16
≥35
≥50
≥95
≥95
≥120
≥185
≥240
American
Standard (AWG)
≥8
≥4
≥1
≥0
≥00
00
≥000
0
≥250
kcmil
≥400
kcmil
≥500
kcmil
PV input
Max Current (A)
60
National
Standard (mm2)
≥25
American
Standard (AWG)
≥2
Table 9 Reference List of Power Cable
4.10 System Wiring:
1. Please make sure all external distribution switches of the Energy Server are disconnected and put
the “N
o Closing
”
warning signs to prevent others from using the switches wrongly.
2. Open the front door of the Energy Server to make sure that the input switch of the Energy Server is
in
“OFF”
state.
3. Connect the protective grounding cables and other necessary grounding cables to the connectors
of the ground lines at the bottom of the Energy Server's power supply equipment.
4.
Connect the “R
,
S, T and N” ports of the BYP INPUT (bypass input) terminal bo
ard with the
corresponding
“
R
,
S, T and N
”
ports of the external BYP INPUT power switch or breaker in the correct
phase sequence and then fasten them.
5.
Connect the “R
, S, T and N
”
ports of the AC INPUT (rectifier input) terminal board with the
corresponding
“
R, S, T and N
”
ports of the external BYP INPUT power switch or breaker in the correct
phase sequence and then fasten them.
6.
Connect the “R, S, T”
ports of the AC INPUT (rectifier input) terminal board with the corresponding
“
R, S, T and N
”
ports of the external AC INPUT (rectifier input) power switch or breaker in the correct
phase sequence and then fasten them.
7. Connect
“
BAT +
”
and
“
BAT -
”
ports of the Energy Server to the output
“
+
”
and
“
-
”
poles of the
battery.