CENTAURI ENERGY SERVER
User Manual - Model 30-2017/12/18-VERSION 1.0
14
Maximum voltage
415V±1%
Maximum charging
current [A] within
1
2
25
38
50
62
75
the permitted range
of battery capacity
Rated current (A)
1
5
30
45
60
76
91
Server voltage
Three-phase-four-wire+G 380Vac
Phase voltage setting
220-230-240Vac (Set by background)
Output voltage
±1%
accuracy
Transient voltage
±5%
range
Transient recovery
20ms
time
Rated frequency
50 Hz / 60Hz±1% (Set by background)
Frequency tracking
50H/60Hz±3 Hz
range
Peak factor
3 : 1
Waveform
Sine wave
Waveform distortion
≤3% (Linear load)
Server
factor
Voltage imbalance
±3% (100% Unbalanced load)
≥105%-110%: After 1 hour, switches to bypass. Automatically
returns to Server when load is restored to normal.
≥110%-125%: After10mins, switches to bypass. Automatically
returns to Server when load is restored to normal.
Overload
≥125%-150%: After 1 min, switches to bypass. Automatically
returns to Server when load is restored to normal.
≥150%: The system will shut down after 10 seconds and the
user should confirm after load reboot.
≥200%: The system will shut down after 2 seconds and the
user should confirm after load reboot.
The system starts up limited current operation &
Short circuit
immediately shuts down, while the user should confirm the
boot
Maximum
efficiency %
≥
9
0
%
≥91%
≥92%
≥92%
≥93%
≥93%
Rated voltage (V)
Three-phase-four-wire +G 380Vac
Bypass
Voltage range
±20%
Rated frequency (Hz)
50/60Hz±5Hz
Maximum current
1
9
38
57
76
95
114
Battery
Terminate
Discharging voltage
315VDC
Management
voltage