INDUSAIL SONIC active acoustic sail system

Technical modifications reserved

 - E1909_08/21

PART II-18

SAFETY

Intended use

The INDUSAIL SONIC plus and INDUSAIL SONIC air lighting sails are used for cooling indoor spaces. The unit is designed 

for non-condensing operation. Consequently, the cold water supply temperature must be selected depending on the 

temperature and humidity of the air drawn into the unit.
The supply air should not fall below the dew point temperature, to prevent condensation on the surfaces of the outdoor air 

plenum box and/or sail. The INDUSAIL SONIC must not be used as a safety-related component or for performing any safety-

relevant function.

Observe the permissible operating and environmental conditions specified in section "Application area" (PART II-3). All 

information contained in these operating and maintenance instructions is based on the currently applicable standards and 

regulations, as well as the latest engineering standards. The manufacturer accepts no liability for damage caused by:

P  

Incorrect use

P  

Failure to observe these instructions

P

  

Installation and operation by untrained technical personnel

P

  

Technical changes to/manipulation of the unit

P

  

Failure to observe the maintenance intervals

P

  

Use of non-approved spare parts

Prevent condensation!

Condensation can occur on the heat exchanger if the cold 

water temperature is below the dew point of the ambient 

air. The Kiefer INDUSAIL SONIC plus is not designed for 

condensing operation. Consequently, it must be ensured 

that the setting for the supply water temperature prevents 

it from falling below the dew point. If necessary, the water 

temperature must be modulated according to the room air 

humidity. The design engineer must take account of this as 

early as the project planning stage.

The following instructions must be observed:

P    

In the case of window ventilation or ventilation without dehumidification, outdoor air with high humidity can 

enter the room when the window is opened, causing the temperature to fall below the dew point of the air. 

It must be ensured that the central cold water controller induces a weather-dependent increase of the cold 

water supply temperature.

P  

It is important to ensure that water pipes and fittings are insulated.

Installation of an on-site dew point and condensation 

monitoring system is recommended for hygiene and safety 

reasons. It must be ensured that the temperature does not 

fall below the dew point at any time.

Содержание INDUSAIL SONIC air

Страница 1: ...Klimatechnik GmbH www kieferklima de en INDUSAIL SONIC active acoustic sail system Technical modifications reserved E1909_08 21 PART I 1 22 TECHNICAL INFORMATION ACTIVE ACOUSTIC SAIL SYSTEM INDUSAIL...

Страница 2: ...Design example for an office 13 Technical data in detail for ventilation cooling 14 Technical data in detail for acoustics 17 PART II INSTALLATION INFORMATION INSTALLATION INFORMATION Application opt...

Страница 3: ...ace design all in one unit Flexible expansion and combination options INDUSAIL LUMINUS INDUSAIL SONIC INDUSAIL SONIC INDUSAIL LUMINOUS plus air silent plus air silent Lighting Ventilation Cooling Acou...

Страница 4: ...ection DN 125 This outdoor air is used to maintain the intended minimum outdoor air flow rate for the room DIN EN ISO 15251 The air flow rate sound power and caloric output are important consideration...

Страница 5: ...w supply air temperatures that can be achieved with this design high cooling capacities are also possible while maximising interior comfort INDUSAIL SONIC silent function description Although this ver...

Страница 6: ...fications reserved E1909_08 21 PART I 6 VERSIONS AND DESIGNS INDUSAIL SONIC plus air silent Light reflectance lll lll lll Ventilation l lll Cooling lll l Sound absorption ll ll lll Installation situat...

Страница 7: ...reserved E1909_08 21 PART I 7 SYSTEM CONSTRUCTION INSTALLATION INDUSAIL SONIC plus air silent Dimensions L x W x H 2500 x 1100 x 255 2500 x 1100 x 250 2500 x 1100 x 50 Max ventilation outdoor air m3...

Страница 8: ...fusers Light reflectance 90 Cooling unit Modular secondary air cooling unit Electrical connection 230 V Controllable EC fan with reliable start up stable performance curve and low noise level Heat exc...

Страница 9: ...the building Acoustic panel Acoustic sail equipped with sound absorbing diffuser material Sound absorbing material 100 polyester Integrated inductive air diffusers Light reflectance 90 Ventilation Ou...

Страница 10: ...be extended or combined as required with the plus or air versi ons Acoustic panel Acoustic sail equipped with sound absorbing diffuser material Sound absorbing material 100 polyester Frame profiles ha...

Страница 11: ...ooling unit filter heat exchanger fan and sound absorber cover plate electrical connection of secondary air cooling unit filter cell air connection cold water connection linear diffuser INDUL P18 acou...

Страница 12: ...IONING Secondary air filter cell DIN EN ISO 16890 ISO Coarse 60 Centrally preconditioned outdoor air flow rate m h 0 to 120 0 to 500 Max primary cooling capacity W 400 1600 Max secondary cooling capac...

Страница 13: ...Office 1 11 10 6 3 4 8 35 35 55 Meeting room 2 4 3 9 4 9 3 40 40 91 Open plan office 2 14 12 5 9 4 4 40 40 65 Numerical values in brackets indicate the minimum requirement or the standard values for...

Страница 14: ...1244 10 0 45 54 518 852 1113 1289 1338 1377 Outdoor air flow rate 0 m3 h U V Pel W LWA dB A Qk W Qk W Qk W Qk W Qk W Qk W 2 0 4 28 358 468 521 539 546 555 4 0 10 37 490 688 793 837 852 881 6 0 22 45 5...

Страница 15: ...a supply air temperature outdoor air of 16 C and an intake temperature of 26 C this value can differ from the ambient air temperature in non condensing operation U Control voltage DC Qk Total cooling...

Страница 16: ...g capacity LWA A sound power level 3 dB A V Air flow rate p Pressure drop Supply air temperature 16 C Intake temperature 26 C sound power level LWA A sound power level L WA dB A 50 45 40 35 30 25 air...

Страница 17: ...of polyester which achieves a particularly high sound absorption at different ceiling distances P Flexible design of office spaces coupled with complex acoustic requirements can be implemented using t...

Страница 18: ...7 0 83 2 27 630 0 68 1 87 0 88 2 41 0 91 2 49 800 0 76 2 10 0 94 2 58 0 90 2 47 1000 0 76 2 08 0 98 2 71 0 87 2 40 1250 0 87 2 40 1 01 2 77 0 92 2 52 1600 0 85 2 35 1 04 2 86 0 96 2 65 2000 0 85 2 34...

Страница 19: ...INSTALLATION INFORMATION ACTIVE ACOUSTIC SAIL SYSTEM INDUSAIL SONIC...

Страница 20: ...esign example for an office 13 Technical data in detail for ventilation cooling 14 Technical data in detail for acoustics 17 PART II INSTALLATION INFORMATION INSTALLATION INFORMATION Application optio...

Страница 21: ...an speed and the position of the water valve so that the cooling capacity of the INDUSAIL LUMINOUS plus meets the current requirements This allows energy costs to be minimised while maximising comfort...

Страница 22: ...ounting threaded rod rubber grommet for power lead mounting of secondary cooling unit at acoustic sail with hexagon nut M8 detail Y 1148 572 875 1207 750 543 780 759 914 112 suspension point suspensio...

Страница 23: ...25 80 158 X suspension point suspension point 875 572 678 470 1148 780 suspension point air connection air connection Y W suspension point suspension point suspension point 2500 1100 INDUSAIL SONIC ai...

Страница 24: ...difications reserved E1909_08 21 PART II 6 TECHNICAL DRAWINGS AND INSTALLATION INFORMATION 2500 1100 INDUSAIL SONIC silent X suspension point suspension point M8 detail X suspension point detail Y 875...

Страница 25: ...l expansion bolt and threaded screw M8 air sail installation height 260mm concrete ceiling Suspension of INDUSAIL SONIC plus Suspension of INDUSAIL SONIC air Suspension of INDUSAIL SONIC silent instal...

Страница 26: ...anges in size The transmission of vibration and structure borne noise to the building structure must be prevented as this can lead to acoustic problems P The installed unit must not be used as a suppo...

Страница 27: ...the secondary air cooling unit as shown in the technical drawing PART II 4 The cut out sections in the cover panel of the acoustic sail must be situated below the respective openings of the fan and th...

Страница 28: ...P With a control signal of 10 V the maximum power consumption of each unit during operation is 45 W P The cables used for switching the EC motor must be shielded PE N L 10V GND 0 10V Tacho 10 1 10 3...

Страница 29: ...connections fan motor Internal connections Designation Colour Function assignment 10 1 PE Green yellow Earth conductor 10 2 L Black Voltage supply 230 VAC 50 60 Hz see type plate for voltage range 10...

Страница 30: ...e established based on the enclosed wiring diagram PART II 11 P The filter cells are attached to the unit and do not exhibit any soiling or damage P The mains voltage control voltage and frequency mus...

Страница 31: ...ork Ensure that the unit is secured against reconnection at a suitable point in the area of the on site power supply Danger due to rotating parts There is a risk of injury from the rotating fan impell...

Страница 32: ...of the acoustic sail ensures ease of access for maintaining and inspecting the unit VDI 6022 Figure 3 Undoing the nuts M8 Opening the acoustic sail Applies only to the INDUSAIL SONIC plus Overhead haz...

Страница 33: ...he fan is maintenance free If you nonetheless detect any soiling of the fan impeller surface during the visual inspection you can wipe it with a damp cloth The fan must be replaced in the event of dam...

Страница 34: ...st be complied with here Examples of such topics include damage to the unit or building services Risk of overhead hazard Indicator of a risk due to an overhead hazard which can result for example duri...

Страница 35: ...or partially opened state as earth connections may have been interrupted Danger due to sharp edges Risk of cuts from sheet metal Sharp edged heat exchanger fins and housing parts In continuous operati...

Страница 36: ...by untrained technical personnel P Technical changes to manipulation of the unit P Failure to observe the maintenance intervals P Use of non approved spare parts Prevent condensation Condensation can...

Страница 37: ...g unit and lighting sail are supplied separately in sturdy transport packaging i e shrink wrapped on one way pallets and secured with plastic or metal bands The installation and or control accessories...

Страница 38: ...ls for air distribution lighting and ceiling systems Lighting calculations using state of the art software tools Development and implementation of control concepts in our own ICE instrumentation contr...

Отзывы: