![Kiefer INDUSAIL SONIC air Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/kiefer/indusail-sonic-air/indusail-sonic-air_technical-information_1966469016.webp)
Kiefer Klimatechnik GmbH
www.kieferklima.de/en
INDUSAIL SONIC active acoustic sail system
Technical modifications reserved
- E1909_08/21
PART I-16
TECHNICAL DATA – DETAILS
V [m
3
/h]
L
WA
[dB(A)]
Q
K
[W]
∆P
[Pa]
250
25
833
10
300
30
1000
14
350
35
1167
18
400
39
1333
23
450
43
1500
29
500
46
1667
35
Q
k
Total cooling capacity
L
WA
A-sound power level (+ 3 dB(A))
V
Air flow rate
∆
p
Pressure drop
Supply air temperature 16 °C
Intake temperature
26 °C
sound power level - L
WA
A-sound power level L
WA
[dB(A)]
50
45
40
35
30
25
air flow rate V [m³/h]
250
300
350
400
500
25
30
35
40
45
50
15
20
10
5
6
7
8
9
250
300
350
400
500
pressure loss Δp [pa]
air flow rate V [m³/h]
pressure loss
200
cooling capacity
1000
1200
1400
1600
1800
600
800
200
250
300
350
400
450
air flow rate V [m³/h]
500
550
total cooling capacity Qc [w]
INDUSAIL SONIC air