Datasheet 2.50-40.051-71-EN
SBM51/06
Product Description
Parameter Reference Table
Software Menu M090 and CD_SB51: /02, /04, /06, /08, /10, /12, /14, /16 --- Danfoss frequency
inverters FC-102/FC-202, FC-301/302, VLT Micro Drive FC 51
Para
meter
DDC Parameter Text
Meaning
FC-102/
FC-202
Data Points
FC-301/
FC-302
Data Points
VLT Micro
Drive FC 51
Data Points
2211
Analog actual value 2
Active parameter set
0-10
0-10
0-10
2253
Analog actual value 7
Analog input
terminal 54
16-54
16-64
-
2254
Analog actual value 8
Motor voltage
16-12
16-12
16-12
2255
Analog actual value 9
Minimum setpoint
3-02
3-02
3-02
2256
Analog actual value 10
Maximum setpoint
3-03
3-03
3-03
2240
Q analog setpoint 1
Parameter set
selection, actual
value mode
Control word.
13/14
Control
word. 13/14
Control word.
13/14
2241
Q analog setpoint 2
Minimum setpoint
PS2
3-02
3-02
3-02
2242
Q analog setpoint 3
Maximum setpoint
PS2
3-03
3-03
3-03
2222
Digital actual value 1
Mains phase error
Warning
word. 14
Warning
word. 14
Warning
word. 14
2224
Digital actual value 2
Thermal warning
State word. 15 State word.
15
State word.
15
2225
Digital actual value 3
Voltage high/low
State word. 13 State word.
13
State word.
13
2226
Digital actual value 4
Not in freq. range
State word. 10 State word.
10
State word.
10
2227
Digital actual value 5
Dig. input terminal
32
16-60
16-60
-
2228
Digital actual value 6
Dig. input terminal
33
16-60
16-60
16-60
2216
Q digital setpoint 1
Relay 1 on
Control word.
11
Control
word. 11
Control word.
11
2220
Q digital setpoint 2
Relay 2 on
Control word.
12
Control
word. 12
(only for
FC-302)
-
2245
Q digital setpoint 3
Activate relay
5-40
5-40
5-40
2246
Q digital setpoint 4
DC brake
Control word.
02
Control
word. 02
Control word.
02
2217
Operating mode
Stop, manual, auto-
matic
State word.
11/09
State word.
11/09
State word.
11/09