A
Page 22 / 26
Product Description
SBM51/06
Datasheet 2.50-40.051-71-EN
Comparison Tables for the Software Menu M090 and CD_SB51: Parameter - Data Points
Parameter Reference Table
Software Menu M090 and CD_SB51: /01, /03, /05, /07, /09, /11, /13, /15 --- Danfoss Frequency
Inverters VLT 6000, VLT 5000, VLT 2800
Para
meter
DDC Parameter Text
Meaning
VLT 6000 Data
Points
VLT 5000 Data
Points
VLT 2800 Data
Points
2210
Analog actual value 1
FI type
621
621
621
2211
Analog actual value 2
Voltage type
621
621
621
2212
Analog actual value 3
Service life
600
600
600
2251
Analog actual value 4
Operating time
601
601
601
2215
Analog actual value 5
Rated motor
speed
106
106
106
2252
Analog actual value 6
Speed calculated
-
-
-
2253
Analog actual value 7
User-defined
display
513
558
-
2254
Analog actual value 8
Relative rotary
frequency
State word/
output
frequency
State word/
output
frequency
State word/
output
frequency
2255
Analog actual value 9
Absolute rotary
frequency
512
518
518
2256
Analog actual value 10 Motor current
IRMS
514
520
520
2257
Analog actual value 11 Performance
515
522
522
2258
Analog actual value 12 Energy
consumption
602
602
602
2240
Q analog setpoint 1
Relative rotary
frequency
setpoint
Control word/
setpoint
frequency
Control word/
setpoint
frequency
Control word/
setpoint
frequency
2241
Q analog setpoint 2
Minimum
setpoint PS1
204
204
204
2242
Q analog setpoint 3
Maximum
setpoint PS1
205
204
205
2222
Digital actual value 1
Error/malfunction State word. 03/
04
State word. 03 State word. 03/
04
2224
Digital actual value 2
General warning State word. 07 State word. 07 State word. 07
2225
Digital actual value 3
Ready for opera-
tion
State word. 01 State word. 01 State word. 01
2226
Digital actual value 4
switched on
State word. 11 State word. 11 State word. 11
2227
Digital actual value 5
Setpoint reached State word. 08 State word. 08 State word. 08
2228
Digital actual value 6
Warning
Load shedding
-
-
-
2216
Q digital setpoint 1
Motor enable
Control word.
06
Control word.
06
Control word.
06
2220
Q digital setpoint 2
Freewheel stop
Control word.
03
Control word.
03
Control word.
03
2245
Q digital setpoint 3
Malfunction
acknowledgment
Control word.
07
Control word.
07
Control word.
07
2217
Operating mode
Stop, manual,
automatic
State word. 11/
09
State word. 11/
09
State word. 11/
09