Datasheet 2.50-40.051-71-EN
SBM51/06
Product Description
Parameter 2253 on the Frequency Inverter VLT 5000
The “User-defined display” parameter is not available on the FI VLT 5000. Data point 558 (“Motor rpm
x scaling”) is output to parameter 2253/01 “User-defined display”.
Parameter Reference Table
Software Menu M090 and CD_SB51: /02, /04, /06, /08, /10, /12, /14, /16 --- Danfoss Frequency
Inverters VLT 6000, VLT 5000, VLT 2800
Para
meter
DDC Parameter Text
Meaning
VLT 6000
Data points
VLT 5000
Data Points
VLT 2800
Data Points
2211
Analog actual value 2
Active parameter set
002
002
002
2253 Analog actual value 7
Analog input terminal
54
523
530
-
2254 Analog actual value 8
Motor voltage
517
524
524
2255 Analog actual value 9
Minimum setpoint
204
204
204
2256 Analog actual value 10 Maximum setpoint
205
205
205
2240 Q analog setpoint 1
Parameter set selec-
tion, actual value
mode
Control word.
13/14
Control word.
13/14
Control word.
13/14
2241 Q analog setpoint 2
Minimum setpoint
PS2
204
204
204
2242 Q analog setpoint 3
Maximum setpoint
PS2
205
205
205
2222 Digital actual value 1
Mains phase error
Warning
word. 14
Warning
word. 14
Warning
word. 14
2224 Digital actual value 2
Thermal warning
State word.
15
State word.
15
State word.
15
2225 Digital actual value 3
Voltage high/low
State word.
13
State word.
13
State word.
13
2226 Digital actual value 4
Not in freq. range
State word.
10
State word.
10
State word.
10
2227 Digital actual value 5
Dig. input terminal 32
521
528
-
2228 Digital actual value 6
Dig. input terminal 33
521
528
528
2216 Q digital setpoint 1
Relay 1 on
Control word.
11
Control word.
11
Control word.
11
2220 Q digital setpoint 2
Relay 2 on
Control word.
12
Control word.
12
-
2245 Q digital setpoint 3
Activate relay
323 + 326
323 + 326
323
2246 Q digital setpoint 4
DC brake
Control word.
02
Control word.
02
Control word.
02
2217 Operating mode
Stop, manual, auto-
matic
State word.
11/09
State word.
11/09
State word.
11/09