background image

1. Recommended Locations for Smoke Alarms

• Put smoke alarms at both ends of a bedroom hallway or large

room if the hallway or room is more than 30 ft (9.1 m) long.

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or

within 3ft (0.9m) of the highest point (measured horizontally).
NFPA 72 states: “Smoke alarms in rooms with ceiling slopes
greater than 1 ft in 8 ft (.3m in 2.4 m) horizontally shall be locat-
ed on the high side of the room.” NFPA 72 states: “A row of
detectors shall be spaced and located within 3 ft (0.9m) of the
peak of the ceiling measured horizontally” (see figure 2).

• In the garage. Products of combustion are present when you start

your automobile.

• Less than 4” (10cm) from the peak of an “A” frame type ceiling.

• In an area where the temperature may fall below 40ºF or rise above

100ºF, such as garages and unfinished attics; this should also include
electrical boxes exposed to these environments.

• In dusty areas. Dust particles may cause nuisance alarm or failure to

alarm.

• In very humid areas. Moisture or steam can cause nuisance alarms.

• In insect-infested areas.

• Smoke alarms should not be installed within 3 ft (.9m) of the following:

the door to a kitchen, the door to a bathroom containing a tub or
shower, forced air supply ducts used for heating or cooling, ceiling or
whole house ventilating fans, or other high air flow areas.

• Kitchens. Normal cooking may cause nuisance alarms. If a kitchen

alarm is desired, it should have an alarm silence feature or be a photo-
electric type.

• Near fluorescent lights. Electronic “noise” may cause nuisance alarms.

• Smoke alarms are not to be used with detector guards unless the

combination (alarm and guard) has been evaluated and found suitable
for that purpose.

3. Installation Instructions

WIRING REQUIREMENTS

• This smoke alarm should be installed in a U.L. listed or recognized

junction box.  The mounting bracket is equipped to accommodate a
3.5 inch hole spacing on a round electrical box and a double-gang
rectangular electrical enclosure.  All connections should be made by a
qualified electrician and all wiring used shall be in accordance with
articles 210 and 300.3(B) of the U.S. National Electrical Code
ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdiction in
your area. This unit consumes four cubic inches of interior space of
the junction box volume.  This figure should be used when calculating
junction box volume. 

• The multiple station interconnect wiring to the alarms must be run in

the same raceway or cable as the AC power wiring.  In addition, the
resistance of the interconnect wiring shall be a maximum  of 10 ohms.

• The appropriate power source is 120 Volt AC Single Phase supplied

from a non-switchable circuit which is not protected by a ground fault
interrupter.

WARNING:

This alarm cannot be operated from power derived from

a square wave, modified square wave or modified sine wave inverters.
These types of inverters are sometimes used to supply power to the
structure in off grid installations, such as solar or wind derived power
sources. These power sources produce high peak voltages that will
damage the alarm.

Wiring Instructions for Quick Connect Harness

CAUTION! Turn off the main power circuit before wiring the
alarm

• When alarms are interconnected, all interconnected units must be

powered from a single circuit.

• A maximum of 18 Kidde devices may be interconnected in a multiple

station arrangement.  The interconnect system should not exceed the
NFPA interconnect limit of 12 smoke alarms or 18 alarms {12 smoke
and 6 other (heat, carbon monoxide, or similar alarms)}. 

• When mixing models which have battery backup (i12040, i12060,

i12080, 1275, 1276, 1285, 1296, PE120, PI2000, KN-COSM-IB, KN-
SMFM-I, RF-SM-ACDC, HD135F, KN-COB-IC, KN-COP-IC) with models
without battery backup, (i1220, 1235, KN-COSM-I, 120X,
SM120X,CO120X, SL177i) be advised that the models without battery
backup will not respond during an AC power failure.

2. Locations To Avoid

Содержание KN-SMFM-i

Страница 1: ...TTENTION Please take a few minutes to thoroughly read this user s guide which should be saved for future reference and passed on to any subsequent owner Smoke Alarm User s Guide Model KN SMFM I 120V A...

Страница 2: ...TRICAL POWER IT WILL NOT WORK WITHOUT POWER MODELS WITHOUT BATTERY BACKUP WILL NOT OPERATE DURING POWER FAILURE Smoke Alarm Procedure NEVER IGNORE THE SOUND OF THE ALARM Smoke alarms are designed to m...

Страница 3: ...ns 4 Operation and testing 5 Nuisance Alarms 6 Maintenance 7 Limitations of Smoke Alarms 8 Good Safety Habits 9 NRC Information 10 NFPA Protection Standard 72 11 California State Fire Marshal Required...

Страница 4: ...acket is equipped to accommodate a 3 5 inch hole spacing on a round electrical box and a double gang rectangular electrical enclosure All connections should be made by a qualified electrician and all...

Страница 5: ...VER TIGHTEN THE BRACKET SCREWS ENSURE THE MOUNTING BRACKET IS NOT DEFORMED OR STRESSED ONCE IT IS INSTALLED USE ONLY MOUNTING HARD WARE PROVIDED USE OF ANY OTHER MOUNTING HARDWARE MAY CAUSE THE UNIT T...

Страница 6: ...s over ridden and the green LED will function to indicate either AC power is present or Battery backup operation Hush mode The green LED will blink every 3 seconds indicating the smoke alarm is in the...

Страница 7: ...ttery backup will not operate if the AC power has been cut off such as by an electrical fire or an open fuse Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are...

Страница 8: ...ere required by applicable laws codes or stan dards for the specified occupancy approved single and multiple station smoke alarms shall be installed as follows 1 In all sleeping rooms Exception Smoke...

Страница 9: ...M THE SALE OF THIS SMOKE ALARM OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUBSID...

Страница 10: ...QUESTIONS OR FOR MORE INFORMATION Call our Consumer Hotline at 1 800 880 6788 or contact us at our website at www kidde com Kidde 1016 Corporate Park Drive Mebane NC 27302...

Отзывы: