background image

Mobile Homes

Mobile homes built in the past five to seven years have
been designed to be energy efficient.  Install smoke alarms
as recommended in 

Recommended Locations

and Image

2A.

In mobile homes that are not well insulated compared to
present standards, extreme heat or cold can be transferred
from the outside to the inside through poorly insulated
walls and roof.  This may create a thermal barrier that can
prevent the smoke from reaching an alarm mounted on
the ceiling.  In such units, install the smoke alarm on an
inside wall with the top edge of the alarm at a minimum
of 10 cm (4") and a maximum of 30.5 cm (12") below the
ceiling (Image 2A).

If you are not sure about the insulation in your mobile
home, or if you notice that the outer walls and ceiling are
either hot or cold, install the alarm on an inside wall.  For
minimum protection, install at least one alarm close to the
bedrooms.  For additional protection, see Image 1A.

WARNING:  Test your smoke alarm operation after R.V. or mobile
home vehicle has been in storage, before each trip and at least
once a week during use.

Wiring

• This smoke alarm should be installed on a UL listed or

recognized junction box.  All connections should be
made by a qualified electrician and must conform to
article 760 of the U.S. National Electrical Code, NFPA 72
and/or any other codes having jurisdiction in your area.

• The appropriate power source is 120 Volt AC Single

Phase supplied from a non-switchable circuit which is
not protected by a ground fault interrupter.

• The alarm should not be operated on power derived

from a square wave or modified square wave inverter.
These power sources produce high peak voltages that
will damage the alarm.

I n s t a l l a t i o n

I n s t a l l a t i o n

8

7

CAUTION!   Turn off the main power to the circuit before wiring
the alarm.

• For alarms that are used as single station, DO NOT

CONNECT THE RED WIRE TO ANYTHING.  Leave the
red wire insulating cap in place to make certain that the
red wire cannot contact any metal parts or the electrical
box.

• When alarms are interconnected, all interconnected

units must be powered from a single circuit.

• A maximum of 24 Kidde devices may be interconnected

in a multiple station arrangement.  The interconnect
system should not exceed the NFPA interconnect limit
of 12 smoke alarms and/or 18 alarms total (smoke, heat,
carbon monoxide, etc.)  With 18 alarms interconnected,
it is still possible to interconnect up to a total of 6
remote signaling devices and/or relay modules.

CAUTION!  Kidde alarms and accessories CAN ONLY BE
interconnected with other Kidde alarms and accessories.
Connection of these devices to another manufacturer’s
interconnect system, or connection with equipment from another
manufacturer into an existing Kidde system could result in
nuisance alarming, failure to alarm, or damage to one or all of
the devices in the interconnect system.

• When mixing models which have battery backup with

models without battery backup, be advised that the
models without battery backup will not respond during
an AC power failure.

• For more information about compatible interconnect

units and their functionality in an interconnect system,
visit our web site at: www.kidde.ca

• The maximum wire run distance between the first and

last unit in an interconnected system is 305 m (1000').

• Image 3 illustrates interconnection wiring.  Improper

connection will result in damage to the alarm, failure to
operate, or a shock hazard.

• Make certain alarms are wired to a continuous (non-

switched) power line.  NOTE: Use standard CSA listed
household wire (18 gauge or larger as required by local
codes) available at all electrical supply stores and most
hardware stores.

820-0612_RevA_1276_MAN_ENG  11/17/03  9:44 AM  Page 6

Содержание 1276CA

Страница 1: ...120 V AC and 9 V Battery Backup Smoke Alarm with Test Button and Hush Control Feature Alarm Manual Model 1276CA SINGLE AND OR MULTIPLE STATION SMOKE ALARM...

Страница 2: ...ranty for service WARNING Removal of the smoke alarm battery and disconnecting or loss of AC power will render the smoke alarm inoperative ELECTRICAL RATING 120 V AC 60 HZ 80 mA maximum per alarm maxi...

Страница 3: ...iances are operated i e portable heaters or humidifiers Locate an alarm in every room where someone sleeps with the door closed The closed door may prevent the alarm from waking the sleeper Smoke heat...

Страница 4: ...ticles may cause nuisance alarms or failure to alarm Extreme temperatures may effect the sensitivity of the alarm Do not install in areas where the temperature is colder than 4 4 C 40 F or hotter than...

Страница 5: ...wer to the circuit before wiring the alarm For alarms that are used as single station DO NOT CONNECT THE RED WIRE TO ANYTHING Leave the red wire insulating cap in place to make certain that the red wi...

Страница 6: ...in Wiring attach the mounting plate to the electrical box Image 4B To ensure aesthetic alignment of the alarm with the hall way or wall the A line on the mounting plate must be parallel with the hall...

Страница 7: ...g sure that the locks on the connector snap into place Push the excess wire back into the electrical box through the hole in the center of the mounting plate Install the alarm on the mounting plate an...

Страница 8: ...ctor and locate the small cut out in the middle of the product label on the back of the unit With a small screwdriver or similar tool slide the switch towards the direction indicated by the arrows Ima...

Страница 9: ...stion are still present the alarm will sound again The Hush feature can be used repeatedly until the air has been cleared of the condition causing the alarm Pushing the Test button on the alarm will e...

Страница 10: ...the battery but it is not necessary This smoke alarm has a convenient front load battery feature that does not require disconnection for changing the battery Testing CAUTION Due to the loudness 85 de...

Страница 11: ...ed on the back of the alarm This smoke alarm uses a 9 V carbon zinc battery alkaline and lithium batteries may also be used A fresh battery should last for one year under normal operating conditions U...

Страница 12: ...nnot provide an alarm if smoke does not reach the alarm Therefore smoke alarms may not sense fires starting in chimneys walls on roofs on the other side of a closed door or on a different floor Fire S...

Страница 13: ...ly by your escape plan Every second counts so don t waste time getting dressed or picking up valuables In leaving don t open any inside door without first feeling its surface If hot or if you see smok...

Страница 14: ...modified abused or altered after the date of purchase or if it fails to operate due to improper maintenance or inadequate AC or DC electrical power The liability of Kidde or any of its parent or subsi...

Отзывы: