I-3
August 1999
76-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
TITLE
Installation Wiring Diagram CCM/
Display & Control Assembly
(
PEGAsys
)
DRA
WING No.
06-235443-001
REVISION
AD
SHEET
2 of 4
18 AWG
800
220
340
3. ALL RELAY OUTPUTS (VOLT/FREE RELAYS AND V/F RELAY) ARE RATED
BETWEEN THE CONTROL HEAD AND THE CONTROL PANEL TERMINAL
6. TO GUARANTEE THE REQUIRED VOLTAGE AT THE RELEASING DEVICE, THE
EX: TO DETERMINE THE TOTAL LOOP LENGTH, MEASURE THE DISTANCE
2. SOUNDER/RELEASE CIRCUITS ARE RATED AT 24VDC, 2A POWER LIMITED.
370
"ON" TIME
CONTINUOUS
CONTINUOUS
CONTINUOUS
MOMENTARY
CONTINUOUS
MOMENTARY
CONTINUOUS
GROUP
700 mA
458 mA
I max.
240 mA
7. RELEASING OUTPUT DEVICES SPECIFICATION
420 mA
B,D
SOLENOID
GROUP
E,G
890181
486500
FM
897494
899175
DEVICE
2.4 A
A
1.5 A
2.4 A
57 OHM
760
RESISTANCE (min.)
10 OHM
34 OHM
52 OHM
103 OHM
15.9 OHM
10.8 OHM
1570
E,G
525
4. SIGNAL OUTPUT REQUIRE THE USE OF END OF LINE RESISTOR (EOR) -
SUPERVISORY CURRENT - 2.4mA/CIRCUIT
FOLLOWING TABLE SHALL BE USED.
BLOCK, THEN MULTIPLY BY TWO.
RELEASING
DEVICE
SOLENOID
486500
897494
FM
890181
PART NO.
899175
AT 30VDC, 1A.
10K, 0.5W; NOT SUPPLIED WITH PANEL.
200
200
2000
240
500
760
WIRE LENGTH (FT.)
14 AWG
3000
940
1440
380
A
B,D
300
300
12 AWG
1200
150
300
480
120
120
16 AWG
1. JUMPER ARRANGEMENTS FOR SOUNDER 1
SIGNAL SOUNDER
AGENT RELEASE
JP1
JP4
JP2
JP3
NOTES:
ON
OFF
ON
OFF
OFF
ON
ON
OFF
FAULT RELAY
VOLT FREE RELAYS
C
(PROGRAMMABLE)
NO NC
TB1, TB2
V / F RELAY
FAULT
NO NC
C
TB3
- FOR POWER LIMITED CIRCUITS.
- FOR SUPERVISED CIRCUITS.
8. RELEASING OUTPUT DEVICES
REFER TO FENWAL DATA SHEETS
POSITION OF RELAY OUTPUTS DURING NORMAL STANDBY MODE.
9. FOR SPECIFIC SIGNAL DEVICE INFORMATION
SOLENOIDS
75.XXX
L
S
A,B,D,E,G
SOLENOIDS
SPRINKLER
FM GROUPS
486500
899175
897494
890181
AVAILABLE AS PART NO. 06-129520-001 (KIT OF 50).
MAXIMUM OF ONE #12 AWG WIRE PER TERMINAL.
120
300
200
895630
12 OHM
2.0 A
895630
MOMENTARY
895630
486500-01
800
486500-01
2000
3000
1200
CONTINUOUS
240 mA
486500-01
103 OHM
NOTE: THE TROUBLE RELAY CONTACTS
ARE SHOWN IN THE UNPOWERED STATE.
5. IF MP01 IS CONFIGURED AS A RELEASING OUTPUT,
A 220 OHM (5W MIN.) RESISTOR COULD BE USED TO SIMULATE
THE CIRCUIT IF NO SOLENOID IS CONNECTED.