I-26
August 1999
76-100016-001
PEGAsys
Intelligent Suppression Control/Fire Alarm System
TITLE
Installation Wiring Diagram
Addressable Contact Input Device
NO/NC
DRA
WING No.
New Design
REVISION
-
SHEET
1 of 1
MODEL
AI,
N
/O
INSTRUCTIONS
SEE
INST
ALLA
TION
CA
T.
NO.
70-407008-001
SmartOne
TM
FOR
SER
VICE
SEND
TO
:
KIDDE-FENW
AL,
INC.
400
MAIN
S
T.
ASHLAND,
MA
01721
DA
TE
OF
MANUF
ACTURE:
MAX.
INST
ALL.
TEMP
.120
°F
7
6
5
4
3
2
1
06-235578-001
PC
PC
PC
PC
(+)
(-)
(+)
(-)
8
A
SW
B
SW
(+)
LED
(-)
LED
Remote LED
(Optional)
PC Line
In
(+)
(-)
(+)
(-)
PC Line
Out
EOL
(Listed 10K Resistor)
Ω
Typical N.O. Initiating
Devices
See Notes: 1, 2, and 4
See Note 3
Typical N.C. Supervisory
Devices
ALL
TERMINALS
ARE
POWER
LIMITED
7
6
5
4
3
2
1
PC
PC
PC
PC
(+)
(-)
(+)
(-)
8
A
SW
B
SW
(+)
LED
(-)
LED
EOL
(Listed 10K Resistor)
Ω
See Note 3
See Note 7
AI, N/O
AI, N/C
NOTES
1.
Maximum 25
Ω
resistance per wire for
initiating circuit. For a total circuit wiring
resistance of 50
Ω
max.
2.
Terminal connection supports wiring
from #18 AWG (0.75 mm
2
) to #14 AWG
(1.5 mm
2
)
3.
Refer to Control Panel Manual for
addressable loop wiring specification.
4.
Maximum 10 VDC @ 1 mA.
5.
This module will not support 2-wire
smoke detectors.
6.
N/O initiating device circuit is NFPA
Class B/Style B.
7.
Rating on LED circuit: 26 VDC Max. 7
mA Max. If not used leave terminals
open circuit.
8.
All wiring is power limited and super-
vised.
9.
The AI, N/C Device is intended for use
within the control equipment providing
the normally closed contact.
10. The initiating device and remote LED
annunciator (if used) must be located in
the same room as the AI.
11.
Use Listed 10K Ohm end-of-line resistor,
P/N 06-129025-003.