PEGAsys
Intelligent Suppression Control/Fire Alarm System
August 1999
76-100016-001
2-2
simulated LCD display readouts. The LCD display readouts
will be used to aid users in the operation of the system.
2-2.2
Audible Device
The Display Panel also contains an audible device which gen-
erates two separate audible tones, one for alarms and one for
troubles. This device sounds continuously when a new alarm
condition is received until the condition is acknowledged. It also
sounds intermittently when a trouble, supervisory, or pre-alarm
condition is received until the condition is acknowledged.
2-2.3
Control and Indicator Description
Refer to Table 2-1 for complete description of controls and indi-
cators.
2-3
SYSTEM SECURITY
The
PEGAsys
system provides three distinct levels of program
protection, as required by UL Standard 864. The user can only
access the system by entering a valid password. Typical valid
passwords consist of three or four characters but may be up to
eight characters in length.
2-3.1
Levels of Security
The three security levels are: Level One, Level Two, and Sys-
tem Manufacturer. The highest security level is reserved for the
system manufacturer. System owner is level one, system in-
staller is level two. Passwords consist of numeric characters (0
- 9) which allows access from the integral keypad of the CCM.
Alphanumeric characters can only be used with the PCS pro-
gram and if used they will lock out any possible entry using the
CCM keypad to gain entrance to the menus.
If alphanumeric passwords are necessary for a particular appli-
cation, it is recommended that the Level One password be nu-
meric and the Level Two password be alphanumeric so as to
allow the user to retrieve system information (system informa-
tion lists) and also prevent a user from changing any pro-
grammed system parameters.
2-3.2
Default Passwords
The
PEGAsys
system provides protection from unauthorized
entry to the system menus by utilizing two levels of default pass-
words, level one and level two. This feature provides two sepa-
rate passwords which increases the security of the system.
Default passwords are set when the system is shipped from
Kidde. These default passwords are:
Level One = 987
Level Two = 1865
These default passwords are valid until other passwords are
programmed into the system.
2-3.3
Entering Passwords
The password entry procedure is listed below:
a.
Verify that the system status is displayed.
b.
Press 0 (zero) key. Verify that the display reads:
PLEASE ENTER PASSWORD
c.
Type in three or four digit password into keypad. Ensure a
pound sign (#) appears for each key pressed.
NOTE:
Use the default password, if a new password has not
been set.
d.
Press the return
(↵
↵↵
↵↵
) key. Verify that the display reads:
1:ISOLATE
2:LIST
3:SET
4:TEST
2-4
SYSTEM POWER-UP
The following step-by-step procedure is for initial power-up of
the CCP.
a.
Perform the installation check-out procedure in Chapter 7
of this manual.
b.
Set the circuit breaker for the CCP power to ON. Verify that
the display reads "Main Processor Power On" and that the
CPU ERROR indicator is lit. Ensure that the audible device
is buzzing continuously.
c.
Press the display module reset switch. Verify that the CPU
ERROR indicator is extinguished and the audible device is
silenced.
d.
Verify that the display reads as follows:
MAIN PROCESSOR
POWER ON
e.
After ten seconds, verify that the display reads as follows:
RXTX NON-MONITORING TROUBLE ON
RXTX1
NOTE:
For multi-loop systems only. The above and below RX/
TX messages will repeat themselves for each RX/TX
module installed in the system. The above message
will be displayed while the system is initializing itself.
This initialization can take up to 90 seconds.
To clear the below RX/TX message use the AutoLearn
function from the menu function or upload the
configuration from the PCS program. If using PCS
software, verify that the correct number of RX/TX loops
are enabled in the Loops Topic of the configuration file
prior to uploading.
RX/TX 1 NOT REGISTERED ON
RX/TX LOOP 1
f.
Verify that the POWER ON and TROUBLE indicators are
lit.
g.
Connect the backup batteries to the CCP in accordance to
the procedure in Chapter 7.
h.
Press the ACKLDGE pushbutton. After approximately one
minute the display will momentarily read :
RXTX NON-MONITORING TROUBLE OFF
i.
Verify the display reads the incorrect time and date.
j.
Set time and date as follows:
(1) Press 0 (zero) key. Verify that the display reads:
PLEASE ENTER PASSWORD
(2) Type in the default 1
st
level password (987).
(3) Press the return (
↵
) key. Verify that the display reads: