B-3
September 2004
Argonite
®
Engineered Fire Suppression System
38-KFSARG-000
Table B-3. Total Flooding Quantities, Volume Requirements of Argonite
(US Standard, kg/ft.3)
Temperature
(°C)
Design Concentration
(% by Volume)
34
38
40
42
46
50
54
-20
0.02404
0.02765
0.02955
0.03151
0.03565
0.04010
0.04492
-10
0.02295
0.02642
0.02827
0.03013
0.03407
0.03829
0.04294
0
0.02199
0.02529
0.02706
0.02883
0.03259
0.03668
0.04109
10
0.02107
0.02422
0.02586
0.02759
0.03123
0.03513
0.03936
20
0.02019
0.02323
0.02479
0.02648
0.02991
0.03365
0.03770
30
0.01935
0.02228
0.02379
0.02538
0.02874
0.03232
0.03620
40
0.01858
0.02141
0.02284
0.02437
0.02758
0.03104
0.03476
50
0.01789
0.02058
0.02195
0.02343
0.02650
0.02981
0.03341
60
0.01722
0.01978
0.02111
0.02254
0.02550
0.02867
0.03212
70
0.01657
0.01904
0.02032
0.02171
0.02454
0.02761
0.03096
80
0.01595
0.01834
0.01957
0.02092
0.02366
0.02659
0.02979
90
0.01536
0.01770
0.01887
0.02015
0.02280
0.02564
0.02872
100
0.01482
0.01704
0.01821
0.01946
0.02198
0.02473
0.02771
110
0.01430
0.01645
0.01756
0.01874
0.02122
0.02385
0.02674
120
0.01383
0.01591
0.01696
0.01813
0.02049
0.02304
0.02585
130
0.10335
0.01536
0.01641
0.01750
0.01980
0.02227
0.02495
Concentration Required: _________________%
Содержание Argonite
Страница 2: ......
Страница 4: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 62: ...6 30 July 2004 Argonite Engineered Fire Suppression System 38 KFSARG 000 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...9 12 September 2004 Argonite Engineered Fire Suppression System 38 KFSARG 000 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 114: ...B 4 September 2004 Argonite Engineered Fire Suppression System 38 KFSARG 000 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 116: ...KIDDE FENWAL Inc 400 Main Street Ashland MA 01721 Attn Documentation Manager Place Stamp Here FOLD FOLD ...
Страница 117: ......