TM0066
Page 37 of 39
Issue 2.01
CHAPTER 6
VOLTAGE AND CURRENT CALCULATIONS
NOTE In an alarm condition this is measured with a 680 ohm resistor connected across
the zone. The maximum zone current has been measured with a 250 R
resistor across the zone. The minimum zone current has been measured
with a 1k 3 resistor connected across the zone.
6.1
2 ZONE PANEL
Mains on (Battery voltage at 24 volts, control voltage at 28 volts)
Quiescent current:
101 mA
Alarm current:
237 mA
Max. zone current:
45 mA
Min zone current:
10 mA
Mains on (Battery voltage at 24 volts, control voltage at 23.1 volts)
Quiescent current:
87 mA
Alarm current:
179 mA
Max. zone current:
40 mA
Min. zone current
10 mA
Mains on (Battery voltage at 18 volts, control voltage at 17.8 volts)
Quiescent current:
70 mA
Alarm current:
137 mA
Max. zone current:
29 mA
Min. zone current:
10 mA